2026-09-08 - EAB Data Center Subcommittee
Summary
Written from the auto-generated captions; names and numbers may be misheard. The first ten minutes of the recording have no captions.
- The Environmental Advisory Board's Data Center Subcommittee heard two University of North Carolina professors: one on how data centers get electricity, one on air quality and health. No votes were taken.
- Energy talk: AI-driven demand is expected to drive most national load growth through 2030, while new transmission can take about ten years. Data centers therefore look to on-site (behind-the-meter) power: diesel, natural gas, batteries, and solar as a partial supplement. Diesel is favored because fuel is easy to store, but it has the highest greenhouse gas emissions and noise levels above 100 dB for larger units; battery storage is far quieter. Behind-the-meter generation can sidestep utility climate goals, and Virginia's new data center tariffs (starting January 1, 2027) were cited as a model for charging large loads.
- Air and health talk: the speaker listed environmental concerns (noise, heat, water use, forever chemicals, fire risk, land conversion, e-waste) and focused on fine particles (PM2.5) and nitrogen dioxide, with health effects from asthma to heart and brain harm. A study under peer review projects large national health costs from data center growth by 2028.
- The speaker's own modeling of the withdrawn 300-megawatt New Hill campus (190 acres between US 1 and Old US 1, four 200,000-square-foot buildings) used federal dispersion software with assumed generator layouts, since the developer never reached permitting. Modeled one-hour nitrogen dioxide peaks exceeded the 100 ppb standard near the site in the diesel scenarios, and doubling capacity for redundancy made it worse; he stressed that results depend on configuration and run time.
- Asked whether any hyperscale data center could avoid health effects on Apex residents, the speaker said not with current technology.
- Board members discussed what the town can do: the state controls air permits, so the town would focus on zoning conditions (generator standards, fuel type, distance from schools, hospitals and recreation, site layout) written alongside the Unified Development Ordinance amendment. Data centers would likely be limited to a heavy industrial zone that does not yet exist on the map. A member noted the earlier proposal had only emergency backup generation, not on-site primary generation.
- Next: a resident call on Teams on September 9 at noon, and the next subcommittee meeting on October 7, on noise.
Issues discussed
Sources
Video
Transcript
These are auto-generated captions; names and numbers may be misheard.
Transcript
00:48How are
10:43It's 5:' I'm going to go ahead and call
10:45to order the September 8th data center
10:49subcommittee meeting of the
10:51environmental advisory board. Welcome
10:53everybody. And with that, I will hand it
10:55over to Bruce for introduction.
10:59Good evening subcommittee members. Uh
11:01today this is our second meeting in
11:03September. We're getting to talk more
11:04about environmental impact especially
11:05that for data centers and other indust
11:07heavy industrial uses. We have two
11:09special speakers for you today. Um the
11:11first presenter uh this is going to be a
11:13little different than what's on your
11:13agenda. I apologize I arranged the
11:15slides slightly different. Uh your first
11:17presenter will be Dr. Noah Kitner. He's
11:19with the University of North Carolina
11:21and the second speaker will Dr. Sarra um
11:23Anu Chalum from the University of North
11:25Carolina as well. So just a little
11:27background about Dr. Kitner. Um he
11:29studies energy systems at multiple
11:31scales from regional to inter uh
11:33international power grids to community
11:35micro grids. Uh his research includes
11:37energy systems planning in different
11:39areas, battery assessment and electric
11:41vehicles and energy storage as well.
11:44He'll be coming up to speak to you today
11:45about energy system sustainability and
11:47human health topics related to data
11:49centers. So Dr. if you don't mind coming
11:51up.
11:57>> Thank you.
11:58>> Yeah. [clears throat]
12:00Okay. Thank you very much uh for having
12:02me and inviting me to speak with you
12:04today about on-site and grid connected
12:06energy for data centers. Um,
12:11as as mentioned, um, I'm a pro, uh,
12:14associate professor in environmental
12:16sciences and engineering at UNCC Chapel
12:18Hill, and I'm also, uh, director of the
12:22energy transition initiative in UNCC's
12:24institute for the environment.
12:26Uh so my research focuses on energy
12:30systems particularly I'm looking at
12:33battery storage systems and other uh uh
12:37technologies that are needed to uh trans
12:40transition the grid toward uh cleaner
12:43and more uh healthier alternatives.
12:47[clears throat]
12:48So uh I've been asked to talk a bit
12:52about on-site generation and different
12:56electricity options for data centers. Uh
12:59so uh today I'll go through uh a little
13:03about the energy system, what's
13:05happening in terms of energy demand and
13:08load growth. Then I'll talk more about
13:12uh grid impacts and why uh data center
13:17operators are more likely to seek
13:19on-site generation than other uh types
13:23of loads. And then we'll think about u
13:26sustainability considerations. So
13:31this is actually a very broad macroscale
13:33view of the whole United States energy
13:36system uh from 2024 from Lawrence
13:39Liverour National Labs uh view of the
13:42energy system. And what you can see is
13:46that on the left side you have all the
13:48different uh primary sources of energy
13:51for the US. In the middle you have uh
13:56electricity generation and it's broken
13:58down. Okay. And it's broken down into
14:03[clears throat]
14:04different sectors going from residential
14:08to uh commercial, industrial and
14:11transportation sector. Uh and
14:15it's all proportionally allocated. So
14:18one thing you might notice is about 2/3
14:22of the energy in the US energy system is
14:26rejected energy in the form of waste
14:28heat. Um and that energy is lost uh
14:33through the system. You also have um
14:38about 32 quadrillion BTUs. So everything
14:42is in uh quads of uh electricity
14:46generation. Part of the challenge uh in
14:49a lot of sectors is that there's a lot
14:51of pressure to increase electricity
14:54generation from different sources and
14:57use that in in different sectors. Uh so
15:00uh some data centers depending on how
15:02they may be classified could be
15:04industrial or uh commercial loads and uh
15:10you can see that electricity feeds a lot
15:12of that uh energy. There's also
15:16natural gas and petroleum used for
15:19heating. So this is a very macroscale
15:21view but I think it's important because
15:23it informs how uh data centers are
15:27thinking about where uh energy will come
15:30from and it shows that there may be some
15:33constraints uh related to where um
15:37electricity is is coming from. So uh
15:40we've seen that advances in artificial
15:43intelligence in particular has led to
15:46massive computational needs and uh
15:50created uh a lot of uh forecasts to show
15:54that uh the US is about to enter a
15:57period of of time where the demand for
16:00energy is rising after the past uh 10
16:05years or so where it hasn't um been
16:07growing as much uh this may
16:13require new planning and and regulatory
16:16frameworks to think about uh aspects of
16:20reliable electricity. So, everyone wants
16:23reliable electricity uh for their homes
16:27and businesses and so uh in order to
16:31maintain a reliable grid. Now, there's
16:33new pressures not just from increasing
16:36demand but also uh climate change and
16:39and weather events and other issues that
16:42are uh affecting the uh frequency of of
16:47power outages and uh on the grid. So um
16:53that's where uh different data centers
16:57are looking toward uh solutions to get
17:00electricity. And that's um where they're
17:04looking at potentially colllocating
17:08generation on site or providing some
17:11grid services like flexibility. It um
17:14I'll explain more about what I mean by
17:16grid flexibility. Uh but those are not
17:20really well understood by research in
17:22terms of how they'll affect uh the
17:26electric grid and rate payers since it's
17:30quite a complex uh system and uh there's
17:36not not much experience. Um but there
17:38have been several studies to look at
17:41where electricity consumption at a
17:44national scale is going based on um new
17:48data centers. And under different
17:51forecast scenarios
17:53um there are predictions that it's going
17:56to drive most of the demand growth uh
17:59more than potentially more than 50% of
18:01new growth through the next uh five
18:04years through 2030. And uh that's much
18:09faster more than twice the rate of the
18:11past decade. So this is um very fast
18:15growth and um
18:19grid buildout is much slower than data
18:22center development. So uh there's kind
18:25of a confluence of issues related to the
18:28data centers that are being uh proposed
18:31because a lot of them need a lot of
18:33electricity and other energy services to
18:36be able to operate but um the
18:41developers are uh
18:45not necessarily in
18:48line with all of the utilities because
18:51there's a lot of different
18:53demands on the grid right now. And so uh
18:56some of the issues that have created
18:59bottlenecks uh for using electricity on
19:01the grid include interconnection cues
19:04that are pretty long. So you have to
19:06wait a long time to be able to actually
19:08connect your uh generator uh to the grid
19:11or get permission to uh connect your
19:15large load to the grid which requires
19:17some period of study for reliability and
19:20other environmental issues. There's also
19:23uh some supply chain issues and
19:25different equipment and uh permitting
19:27delays are already there. So with all of
19:30those background issues happening in the
19:32energy sector as data centers are
19:35looking at building new generation,
19:39they're encountering a lot of challenges
19:41around the uh around the country and in
19:45North Carolina too in terms of being
19:48able to figure out how they're going to
19:50get power. That's led a lot of data
19:52centers to pursue looking at uh what are
19:55the on-site generation options available
19:58especially because the cost of
20:00distributed energy resources has
20:02declined and also there's an
20:04availability of other options for them
20:08uh in terms of uh diesel generators and
20:12uh and natural gas turbines which I'll
20:15I'll talk about some of those uh issues.
20:19So with a lot of limited capacity in the
20:23electric grid, the uh
20:27utilities reser planning reserve margins
20:29are decreasing. It's uh threatening the
20:33reliability of the grid and increasing
20:36some costs to operate the grid.
20:39With all those factors in mind, someone
20:42who's operating a data center might want
20:44reliable electricity. And so they're
20:46looking at what can they do to
20:48supplement their own energy demands
20:52uh
20:53to add this generation. So these are
20:55some of the reasons why I think that uh
20:58data centers in particular are adding so
21:01much
21:03electricity generation and other uh
21:06backup energy resources on site either
21:09for um heating or cooling. There's also
21:13I think it's important to distinguish
21:15between different types of data centers
21:17because data centers get get um
21:20classified differently and uh some of
21:23the really energy most energy hungry
21:27data centers are these uh hyperscalers
21:30or AI optimized data centers which are
21:34um used primarily for AI computational
21:38analysis which may be differentiated
21:41from the data centers that are providing
21:43more um backup cloud storage or uh
21:48crypto mining or other uh uses. So uh
21:53there hasn't been
21:55too much work yet to figure out exactly
21:58what those uh different data center
22:01energy demands will look like. But there
22:04have been some studies to um uh begin
22:07examining what happens uh what what are
22:11the risks to the power grid when these
22:14uh data centers arrive. And most of the
22:17risks could be categorized into a few
22:20areas ranging from short-term to
22:22long-term risks. So I'd say the short
22:24term you have voltage uh stability and
22:28other uh grid stability issues that
22:31happens on a time scale of seconds to
22:33minutes to hours. Um making sure that
22:36the frequency on the grid is maintained
22:40at at the same level and that's um more
22:42of a um grid stability issue. Uh there's
22:48also some medium and long-term risks
22:51like uh ensuring that the available
22:55electricity supply is sufficient and
22:58there's uh adequate resources for uh
23:02planning these. So um
23:06the
23:08traditional frameworks to look at
23:11reliability haven't really managed uh to
23:17look at customers that are adding uh
23:21dozens of of megawatts or potentially
23:23hundreds of megawws
23:25uh very quickly on on the grid. And
23:28that's uh causing a lot of uh concern
23:30about how do you actually make sure that
23:33the system stays reliable and functional
23:36uh given those um high loads or where
23:40where will that electricity comes from?
23:42Also just from the um background level
23:46of the electric grid and and system that
23:48we're dealing with right now is that um
23:51there's a long lead time to building new
23:55uh transmission infrastructure. So, um,
23:59one of the reasons that on-site
24:02generation and backup power has gotten
24:05even more, uh, cost effective and data
24:09centers are looking at this more
24:11seriously is that it takes about 10
24:14years to build or potentially more to
24:16build new transmission lines. And so
24:19transmission lines are really not being
24:22evaluated as a serious option to site
24:25new data centers because the the
24:28challenge is it's really costly and
24:30there's already congestion on existing
24:32transmission lines in the grid. So as a
24:35result of really expensive transmission,
24:38uh data center operators are looking at
24:42what can they do to either store or
24:45generate electricity on site to
24:47supplement that. And um there's
24:50different options that they have but
24:52really um motivated by this long time uh
24:58to build transmission infrastructure and
25:00even other um technologies are taking a
25:05long time to build or uh because of
25:08supply chain issues for natural gas
25:10turbines or other generators. But we're
25:13seeing um
25:16plants look at a few different options
25:18for backup or supplemental power. A lot
25:22of the data centers are looking at um
25:25diesel or natural gas, but those are
25:27sight constrained geographically.
25:29Battery energy storage may be an option
25:32for some data centers because um the
25:36planning and and permitting time
25:38typically can be faster than for uh a
25:44gas turbine.
25:46There's also uh challenges if you were
25:49going I mean solar uh or wind may be uh
25:54faster options to to be able to build
25:57but uh part of the challenge is that
25:59they provide variable electricity. So uh
26:02it's not going to necessarily uh provide
26:06uh 247 backup electricity or or um
26:10full-time electricity. it'll supplement
26:12some of the load and could be coupled
26:15with um battery storage or it could be
26:17coupled with diesel or gas turbines. So
26:21different uh types of data centers are
26:23looking at combinations of these options
26:26based on the geography of where they're
26:28looking to build the the site and um
26:32what is is realistically available. So
26:36when we're talking about reliability
26:37challenges, most data center operators
26:40want 59s of reliability. That means uh
26:4499.999%
26:46of the time they should have uh reliable
26:51power. That equates um to um really uh
26:57high level of of reliability. um even
27:01something like 99%
27:04reliability alone amounts to several
27:08hours of outages per year. So that's why
27:13they're really looking at um almost
27:17consistent access to electricity. And in
27:20order to achieve even more nines of
27:23reliability, that's where backup power
27:26options become uh
27:30what what data centers are looking at to
27:32be able to um meet these and that's
27:35where I think there are different
27:37challenges from the uh electricity side
27:39and looking environmentally at what are
27:41the impacts of these systems because um
27:44your your options for backup power
27:47especially when um the grid electricity
27:51is not available usually have
27:53traditionally uh focused on diesel
27:56generators or natural gas turbines. The
28:00limitation with natural gas is that
28:03there's not pipelines everywhere and um
28:08the storage of natural gas could be
28:12difficult on site. Uh so while diesel
28:16might look more expensive as a fuel on
28:18paper, a lot of uh companies will look
28:22at diesel as an option because the
28:25generator itself is around the same uh
28:28cost but the fuel can be stored easily
28:32more easily on site. It may require
28:35being trucked in uh on roads. So there
28:38may need to be roads but the same
28:40pipeline infrastructure is not as
28:42necessary. It's a more energy dense fuel
28:45than natural gas. So logistically
28:48because uh diesel can take up less
28:51space. Uh that that's one reason why
28:55diesel is being uh projected. There's
28:58definitely challenges environmentally
29:00with using diesel and um we'll hear more
29:04about some of the particulate matter
29:06impacts and other um air pollution
29:09impacts of using diesel. Typically,
29:12diesel might be used for backup power or
29:15potentially during periods where grid
29:18electricity is really expensive or more
29:20expensive and it becomes less expensive
29:22to operate your backup generation. For
29:25diesel, that that seems rare, but for
29:27natural gas turbines, that could be um
29:31pretty that that could uh the power
29:34prices are fairly volatile. And so there
29:36could be periods where um it makes sense
29:39to run natural gas. uh onsite which is
29:43considered kind of behind the meter and
29:45and these are all what I would consider
29:48behind the meter options because from
29:50the utilities perspective they wouldn't
29:53necessarily
29:55uh see or interact with those generation
29:58options. The other uh contenders for
30:03behind the meter on-site generation
30:05include battery storage, which could
30:08reduce um peak loads and is a an
30:13opportunity to store electricity and do
30:18some kind of price arbitrage
30:21from the perspective of the data center.
30:23uh to
30:25store electricity when it's pretty
30:27inexpensive and then use it later when
30:30electricity might be expensive or not
30:32really available on the grid. It's also
30:36probably a way that we'll see uh data
30:39center operators try to circumvent
30:42different requirements from new tariffs
30:44that are being designed like in
30:45Virginia. So for instance, Virginia is
30:48going to start charging uh different
30:50data centers a fee based on their uh
30:54peak capacity and their peak grid
30:57connection request. If you install um
31:02battery storage or even some combination
31:04of other uh on-site generation, it could
31:07be diesel or natural gas. If you install
31:10those onsite, then you could potentially
31:14uh reduce your grid connection request.
31:17And so there are some economic
31:19incentives and reasons why data centers
31:22may uh pursue uh colllocation of adding
31:26some kind of gas turbine or or battery
31:29storage. This could also be supplemented
31:31by something like solar electricity or
31:34or wind. But the challenge with solar
31:37and wind for the data center are that
31:39they might take up more uh space or land
31:43uh to be able to add um
31:47generation. So if uh if they have
31:50available land then they may look at um
31:53using solar as well because it could
31:55reduce or offset some of their um peak
31:58consumption.
32:00I think those are some of the key
32:02motivations for why uh data centers may
32:06be looking at on-site generation. Uh
32:10so
32:13um [clears throat] there have been some
32:15examples of different uh types of
32:18innovations or policies to try to uh
32:23expand uh capacity and protect the grid
32:26reliability uh in PJM Pennsylvania, New
32:30Jersey, Maryland uh grid area. So
32:32they've been looking at ways to try to
32:35speed up interconnections or change the
32:38tariffs that large loads from data
32:41centers face. So that um that's
32:43something that's been happening in
32:45Virginia. And uh then there's been rules
32:48around bringing your own capacity or
32:50generation. So these types of uh setups
32:55are not unique to North Carolina
32:57necessarily, but are happening in other
33:00other states and locations.
33:02And uh there are um
33:08a lot of the the rules are are trying to
33:12figure out who pays for these grid
33:14upgrades or transmission line systems
33:16that um if if the data center is
33:19connected to the grid, they're going to
33:22draw from. But the current tariffs and
33:26uh
33:28frameworks for uh compensating the
33:31utilities are not designed really for
33:35data centers and utilities face big
33:37risks because if they build a lot of
33:40transmission or other infrastructure to
33:42support the data center and then there's
33:45a risk of a stranded asset. If the data
33:47center then decides to stop operations
33:49or um leave, then they've invested in a
33:52lot of um new electricity infrastructure
33:56uh for areas that may not um need it. So
34:01um
34:03there have been some studies to look at
34:05well what if data centers could uh
34:08benefit the grid and serve as an asset
34:12for demand response and to some extent
34:15that's been uh proposed but the the
34:18challenge is that you would have to get
34:21uh utilities and the data centers in
34:23agreement of how much time the data
34:27center is actually going to be
34:28operational and and during which times s
34:31uh data centers would allow uh the
34:35utility to
34:36buy their uh demand or or be able to
34:41ramp them up or down depending on the
34:44grid needs. So um on a day-to-day basis
34:48balancing the grid is really important
34:50and contributes to a large portion of
34:53the operational cost of making
34:55electricity affordable. But then um the
35:00data center is uh
35:04it's it's not clear the extent to which
35:07um the data center will be able to
35:09curtail uh its its load during periods
35:13of uh a demand response setup. So uh
35:18data centers would be able to
35:20participate in these programs more
35:21effectively if they have battery storage
35:24or other systems on site. Um
35:28but that's not always the case. So um
35:36uh essentially like if you have some uh
35:40flexibility which flexibility I would
35:42define as the ability to u ramp up or
35:46down your electricity
35:49uh usage in a very quick manner like
35:53within seconds to minutes. Like if
35:55you're able to do that because you have
35:57on-site battery storage or some other
36:01on-site generation like a gas turbine,
36:05then uh you could benefit the utility in
36:09a way where um the peak demand might be
36:13flexible. And so there could be some uh
36:16mutually beneficial arrangements, but
36:18there also could be some uh situations
36:20where uh it it doesn't really benefit
36:25the utility or the utility gets these um
36:28peak periods. So um
36:32the that that's uh so there are um types
36:37of data data center flexibility options
36:40that that are available and in addition
36:43to uh thinking about grid reliability.
36:47Uh on-site storage or on-site gas or
36:50diesel generation is uh often examined
36:54as a strategy uh to be able to do that.
36:57uh it's faster to build and connect and
37:01um
37:02and so and you don't have to deal with
37:06uh adding much more transmission lines
37:09which can be really costly and uh is
37:13requires coordination across multiple
37:15jurisdictions and stakeholders uh
37:17potentially going across state lines.
37:20Um,
37:22in Texas, a lot of new data centers are
37:25adding battery energy storage for this
37:27reason, for flexibility. And so it's
37:30likely that other data centers will look
37:34at that um because especially
37:37um in states now like in Virginia where
37:40they've changed their tariff structure
37:42where it really incentivizes adding um
37:47battery storage to the data center or
37:49else um the the data centers will have a
37:53lot of um increased costs. So those are
37:57um some of the issues that utilities are
38:01facing right now. Um
38:07so I'll talk a little bit about
38:09Virginia's tariffs and then I'll talk
38:11about the some of the sustainability
38:13considerations. Um in uh Virginia
38:17they've recently or as of so January 1st
38:212027 they'll start implementing new
38:24types of tariffs and uh the main changes
38:29are that instead of having an on- peak
38:32uh demand charge for transmission
38:34systems they'll look at the actual name
38:37plate capacity of uh what's installed at
38:41the uh data center and uh create a uh a
38:46fee based on uh a percentage of the
38:51minimum generation demand billing. and
38:54um
38:56they'll
38:59so there's a considerable upfront
39:01investment that's um going to be
39:05required for new uh data centers there
39:08and it's a new service class whereas in
39:11um North Carolina or other other states
39:14there's not um really a separate tariff
39:18class for for data centers. So that's um
39:22uh an example of things that are
39:24happening. Uh in some of our research,
39:26we've been looking at like what that
39:28actually means for uh data centers and
39:32power generation of what they would
39:34likely do. And so we've simulated some
39:38of the uh typical load profiles for a
39:43hypers scale data center uh which
39:47might peak uh in in the middle of of the
39:51day. But um this is uh based on some
39:55assumptions related to their pretty
39:58consistent utilization rate of 80 80%
40:01and um
40:05and a load of like 500 megawws. So 500
40:09megawatts is a really big uh system and
40:13uh there are different scales of of data
40:15centers. Uh some of the systems being
40:18proposed in North Carolina might um be
40:20much smaller than 500 megawws. Uh but
40:23they still would look at on-site power.
40:27And uh
40:29the other the other option that's not or
40:32the other options that have been
40:33proposed for data centers around the
40:35country but haven't really been utilized
40:39um yet include hydrogen and nuclear. So
40:43hydrogen could be used through a fuel
40:46cell that's on site. Fuel cells actually
40:49can operate similar to a generator and
40:52uh use uh natural gas fuel or hydrogen.
40:57Um hydrogen can be produced in different
41:01ways. So there um there are different
41:05types of hydrogen but um a lot of the
41:09hydrogen economy in the US is more
41:11concentrated in states like California
41:14or or Texas and and not as it's not as
41:18uh common in North Carolina for
41:22instance. And then um small modular
41:24reactors have been proposed as options
41:27for uh colllocation with data centers
41:30but um there's not many operational
41:34projects. Uh one is that they've been
41:37expensive. There's a there's a project
41:39that may be developed in Ohio uh with
41:43New Scale, which is a company that has
41:45developed small modular reactors, but
41:48they're not um
41:51widely seen in existing data centers
41:54that um have already been built across
41:58the US. The reason why uh small modular
42:01reactors have been proposed is that they
42:04could co co-produce both uh electricity
42:07and heat uh which can provide some
42:12cooling energy depending on the systems
42:14that are being used for the data center.
42:17But um
42:21I think there there's a lot of
42:23permitting and other planning challenges
42:25around adding new um small modular
42:30reactors uh for collocation with data
42:33centers. So even though uh they they may
42:36be an option in the future, they remain
42:39fairly expensive uh and probably
42:43uh
42:45unlikely to uh unlikely to be developed
42:50in a in quickly and an economically uh
42:54quick manner. So we're seeing that um
42:58that's where battery storage has has
43:00played a big role. But um there are a
43:03lot of uh issues also with thinking
43:06about diesel or uh natural gas as
43:10on-site generators because they might be
43:12subjected they might not be subjected to
43:14the same uh regulations as typical
43:17facilities that are connected to the uh
43:20power grid depending on their size and
43:23capacity. And so that can lead to um
43:28utilizing them during different times
43:29that violate or that is uh higher than
43:33what is regulated by the clean air act.
43:36And uh some of the concerning emissions
43:40that uh Sarov will talk about more uh
43:43include NOx uh particulate matter PM2.5
43:47carbon monoxide and VOCC's. Also, um
43:51greenhouse gas emissions are are another
43:53issue because if you look at um the
43:56greenhouse gas emissions from uh diesel
43:59versus natural gas versus uh
44:03solar, hydropower or other
44:07wind uh power sources. Um,
44:11diesel, I mean, um, diesel is by far the
44:15highest and, um, averages around 700 to
44:20800, uh, grams of CO2 per kilowatt hour,
44:24whereas natural gas is about, um, uh, 50
44:29or 60% of the those emissions um, from
44:33diesel. uh but uh solar wind even when
44:38backed up by battery storage are much
44:41lower on the order of 20 to 50 grams of
44:45CO2 when you account for all the
44:47manufacturing and construction
44:49requirements. Uh natural gas may be
44:52between 300 to 500 grams of CO2 per
44:56kilowatt hour. So that those are uh
44:58important to think about. Um and then
45:00there's issues of uh the the land
45:04footprint and noise. So um the uh diesel
45:09can often range from uh a small diesel
45:13generator that's only 50 kows goes from
45:1670 to 85 dB. But once they get beyond a
45:20megawatt or 1500 kilowatts in capacity,
45:23they can easily exceed 100 dB. uh gas
45:27turbines that are also typically larger
45:30than a megawatt. Uh we'll go into the
45:33110 to 155 decel range. Uh and battery
45:38energy storage ranges from 0 to 50 dB
45:42depending on the size and cooling fan
45:44components. So, um, if you're looking at
45:47noise as another factor to consider for
45:50on-site generation, I think, um,
45:54there's, uh, quite a big range there.
45:57Uh, so I I wanted to, uh, talk to you
46:00about these different options and then,
46:03uh,
46:06and I gave you an overview of why I
46:08think on-site generation is being uh,
46:11examined more clearly. there are uh
46:15different options for data centers uh to
46:19pursue and they they lead to different
46:22impacts related to their um
46:24environmental concerns and also um
46:26noise. So I'm happy to take any
46:28questions you may have or answer any or
46:31follow up with any discussion. Thank
46:33you.
46:34>> You you mentioned early on about natural
46:37gas storage on site. Uh, how would you
46:41store natural gas on site?
46:44>> Oh, I think that would be very difficult
46:46to do. Um, and that's one of the I I
46:48mean, uh, there's um
46:53that that's why a lot of companies are
46:56looking at diesel as an alternative to
46:58natural.
46:58>> I mean, because the distribution
47:00companies, gas distribution companies
47:02have LG tanks where they
47:03>> Yeah.
47:04>> pull it down. And I don't think that
47:06would be real feasible for
47:08smaller operation.
47:10>> Yeah, I completely agree that and that's
47:12why a lot of um the data centers that
47:15I've seen have looked at diesel even
47:17though if you look at like an energetic
47:19basis, diesel is often way more
47:20expensive as a fuel. So you might think,
47:22oh, why would they even choose diesel
47:24instead of natural?
47:25>> They've got a a gas line going into the
47:28facility, then that would make it
47:30>> that would that would make it work. But
47:31yeah, if you don't if you don't already
47:32have the line, then you have to um
47:34account for the line. Yeah.
47:36>> And as far as battery storage, we're
47:39looking at that is shaving peak loads
47:42for the most part,
47:44not for any kind of primary use
47:47>> mostly. But um but I mean it it's hard.
47:50It depends on what you mean by primary
47:52use. like it's not it's not going to um
47:54completely power the data center on its
47:57own, but I would imagine that if you
47:59have a battery on site, it'll probably
48:01get used every day.
48:03>> Um and so it's going to be charging and
48:07discharging almost daily and uh cycling
48:11through. So that will affect the peak
48:12load, but it will also provide some
48:14supplemental
48:16um reduction during non- peak times as
48:19well. Uh that's compared to a diesel
48:22generator where you might have the
48:25diesel gener generator available on site
48:29but uh it may only get used on peak days
48:34to manage the peak load or it may only
48:36get used in times when there are
48:38reliability concerns. There might be an
48:40outage and for backup power. So the
48:44battery battery may be used for backup
48:47power and maintaining the grid
48:49stability,
48:50but if it's installed on site, it would
48:53likely be cycled almost daily, whereas
48:56the diesel generator probably wouldn't.
48:59>> Okay.
49:02And one one last thing you also
49:04mentioned solar and wind as as possible
49:07options from
49:09>> from a practical standpoint with today's
49:11technology. Is that all that feasible
49:14for unless you have a lot of land mass?
49:18Um so uh there there it is highly
49:22feasible for today not to power the
49:24whole system but a lot of data centers
49:27are looking at adding solar or wind
49:29depending on their geography because
49:31they can shave off their peak demands or
49:34they can use it as a supplemental
49:36source. So, probably not for primary,
49:38but I mean, if you could cover 50 to 75%
49:41of your electricity needs by adding
49:44solar on-site or nearby, then a lot of
49:48places are looking at that because it um
49:51compares with then they have to purchase
49:54less electricity from the utility
49:56company.
49:56>> I'm I'm I'm I've got a myopic view
50:00because I'm looking at at the Apex area.
50:02>> Sure. So, I'm I'm trying to see whether
50:05that those two options would be really
50:08feasible.
50:10>> Um, I mean, yeah, within APE, I mean,
50:13within Apex, I think you could see some
50:15solar on like the the roof of the design
50:18of a possible data center. I think that
50:21would be um a possibility. It would
50:23probably not primarily power the data
50:26center. It would it would be a
50:28supplemental. see how it could primarily
50:30power it but yeah it would
50:32>> provide some supplemental energy.
50:34>> Yeah. Yeah. And it would probably limit
50:36their peak capacity requirement from the
50:39uh from the electric utility.
50:46So with this behind the meter
50:48generation, so like sort of a utility
50:51like Duke, you know, more so in days
50:53gone by, they had climate goals where
50:56they were trying to reduce carbon and
50:57switch sort of their mix to more carbon
51:00neutral.
51:01>> I mean, it's still a state law.
51:03>> Yeah. But when you get to behind the
51:05meter generation like this, would they
51:08sort of be exempt from any of those
51:10goals and it would just be up to the
51:12individual private company?
51:15Well, the the thing about um behind the
51:18meter that well, so um the thing about
51:21behind the meter is if you were big
51:23enough and for a large load like a data
51:26center, it's different than like if you
51:28wanted solar on your house because you
51:30could you could basically um
51:34add a lot of these generation sources
51:37behind the meter because they're not
51:39connecting with or interacting with the
51:42main utility. And if they have the um
51:46switches to basically
51:48choose when they're using uh what's
51:51called self consumption or basically
51:53generating on site, then they could do
51:57that when it's economically feasible and
52:00then buy electricity from the utility
52:02when it's uh during other times. And um
52:08that that is it is possible to do that
52:11without having to negotiate so much with
52:14the utility because they could um
52:18operate those generators and systems
52:21themselves. And so you could
52:25collectively get a bunch of these behind
52:27the meter generators who were just using
52:31just exclusively natural gas and diesel
52:34for power generation.
52:36>> Yeah.
52:36>> And Okay.
52:38>> And then that's behind the meter because
52:41um they're not interacting as much with
52:44the utility. It's harder to probably do
52:45that with natural gas because you would
52:48need the pipeline and dist I mean there
52:52are other
52:54factors but for diesel generation it's
52:56definitely possible to um operate the
53:00diesel generator to uh provide
53:02electricity that then is is not seen
53:05behind the meter basically just refers
53:07to not not like invisible to the
53:11utility. Um and so they're not selling
53:14that power or heat and then they're they
53:19are not um responsible for it,
53:22>> right? So they they themselves even
53:24though they're doing the same thing as
53:27like Duke Energy, they they don't might
53:30not have any climate goals or anything
53:32like that. Definitely they're not
53:34selferving. Yeah, there's there may not
53:36be the same uh yeah, they can circumvent
53:39the the rules of like the carbon plan or
53:42other um emission requirements.
53:46>> Thank you.
53:49>> So, I wanted to say first off um thank
53:51you very much because this actually
53:52helped a lot. The one that was
53:54originally proposed for this area was
53:57300 megawws and there was a discussion
53:59of diesel. So, I'm imagining you trucks
54:02coming in every day. Um, I also
54:05appreciate, you know, that you spoke on
54:07the noise and the, um,
54:10what it would do to the power grid. Um,
54:14I guess my biggest question is what have
54:17you seen with the strains on the power
54:19grids of what they've done to an area
54:22like brownouts or blackouts or things
54:24like that? Um, and
54:29as quickly as this is changing, is it
54:32possible that you could see a developer
54:35coming in putting something down like
54:36this and then within a few years it
54:40rapidly changing that that they need to
54:43up and move somewhere else.
54:47Those are really good questions. I mean
54:50I think uh because of the complex nature
54:53of the power grid it's hard to attribute
54:55some brownouts specifically to the
54:57presence of data centers but if we look
54:59at like historical events that have
55:02happened recently including like winter
55:04storm Yuri in Texas in 2021 there's
55:08definitely pressures on load growth
55:10without and also unc
55:13coordinated risk mitigation for planning
55:15that uh temperatures might go uh very
55:19low during those periods which caused a
55:22rapid rise in demand for electricity at
55:24a time when then there wasn't
55:26electricity and it created this ripple
55:28effect where there were outages for
55:30days. Um that definitely play like this
55:36the constrained supply
55:39can definitely play a role and not and
55:42having these um smaller reserve margins
55:45going forward is a risk that um
55:48increased
55:50large loads on the grid could reduce the
55:52planning reserve margin that's
55:54available. um that could happen in North
55:57Carolina even with other
56:00events with hurricanes or um uh
56:04extreme weather. Um but also so I think
56:07it's there's um compound risks happening
56:10and it's so it's um it's not just the
56:13weather but it's also the reduced
56:17planning reserve margin which is like a
56:19long-term planning horizon uh
56:24during different times. So that that's
56:25definitely a challenge. Um and then uh
56:30yeah there are risks of being st I mean
56:32uh that I think that's what uh Virginia
56:35was trying to do in terms of redesigning
56:38their tariff is um force a lot of the
56:43data centers to pay more of the costs
56:46upfront for a longer period of time. And
56:51so that was thought that that could
56:53potentially reduce the risk that they
56:56could leave in two or three years or you
56:59know go bankrupt and that or you know
57:01just stop and then there was a lot of
57:03and I think from the utility perspective
57:05the reason that would be a problem is
57:08that if you upgraded a lot of um
57:11substations, transformers, other
57:13electrical equipment in that area that's
57:15a major investment and uh if If
57:20[clears throat] you did it in an area
57:21where it's o much more oversized
57:23compared to the load, then um someone
57:27else is going to have to pay for it.
57:31>> Thank you.
57:40>> Thank you so much. Appreciate it.
57:52Thank you, Dr. Kitner. All right, our
57:54next speaker is Dr. Sarab Arunachalam.
57:56He'll be speaking today. His background
57:58is in air quality emissions and modeling
58:00and public health. He's over 20 years of
58:02experience in emissions and air quality
58:03modeling across multiple scales. And
58:05he'll be providing us with a lot of
58:07great information today.
58:11>> Good evening.
58:15Can you hear me? Okay, it's good. Thank
58:17you. Thank you for the invitation,
58:19Bruce, for this um environmental
58:21advisory board and um thanks to see this
58:24board stood up now since the various
58:26town council meetings over the last year
58:28or so. I'm very happy to be here today
58:31and to talk about the environmental
58:32impacts of data centers. Hopefully this
58:34will be a nice complement and picking up
58:36from where Noah um last stopped with
58:39this uh focus on energy and how energy
58:41can be um created for these data centers
58:44and where the environmental impacts may
58:46be. With that, I'm a professor at UNCC.
58:48I direct um a center for environmental
58:50modeling for policy development as well
58:52as the um institute for the environment
58:53where I'm a deputy director um looking
58:55at various aspects of um environmental
58:57impacts uh specifically focusing on both
59:00the environment and subsequent public
59:02health impacts. Here's a picture from uh
59:05what is called as the data alley uh data
59:08center alley. Uh this is Virginia. You
59:10don't have to think too far to guess
59:12where this is taken from. This is one of
59:14the pictures in Luden County in in
59:15Northern Virginia. And you can see a
59:18bunch of data centers uh buildings in um
59:22very very close proximity to residential
59:24neighborhood on the lower right half of
59:26the screen. And then if you zoom into
59:28one of these buildings, you can see um
59:31uh both generators as well as the um
59:33cooling [clears throat] towers on top of
59:34the building. This is how a data center
59:37campus looks like. And I know we were
59:39all looking at the potential um for one
59:42of these to come very close to where we
59:44are today in Apex. So this is what this
59:46could look like um if they were
59:48approved, processed and so on. So what
59:50I'll do over the next few minutes is to
59:52give you sort of a three or fourpart
59:54presentation. first to give a very broad
59:56um national landscape of how this
59:58particular um area or field looks like
1:00:01in terms of data centers and where we
1:00:02are going and then I'll talk about the
1:00:04environmental impacts of what data
1:00:06centers mean and then uh zoom in to our
1:00:10own town of Apex to see what could
1:00:12happen if the proposed and now withdrawn
1:00:15data center was here. Okay.
1:00:18Um just um large big picture from the
1:00:21current national or federal
1:00:23administration. This is from the White
1:00:24House. Uh if you go to ai.gov, you can
1:00:27see this. There is an action plan, a a
1:00:29action plan by the current
1:00:30administration where the broad big
1:00:32picture statement and the focus is the
1:00:34US is in a race, a race to achieve
1:00:37global dominance in artificial
1:00:39intelligence. Whoever has the largest AI
1:00:41ecosystem will set global AI standards
1:00:44and reap broad economic and military
1:00:46benefits. With that, this is focused on
1:00:48three different pillars. The first one
1:00:50is accelerate AI innovation. Second is
1:00:52build AI infrastructure and the third is
1:00:54lead in AI international diplomacy and
1:00:57security. So this is sort of the message
1:00:58that we have from the current
1:00:59administration at the top down in terms
1:01:01of where this country should be going.
1:01:03Okay with that um just a broad picture
1:01:06on terms of where the global electricity
1:01:08growth is. Uh we saw some numbers from
1:01:10Noah earlier. I'll present a different
1:01:12perspective on this but in general you
1:01:14see some very important numbers come out
1:01:16of this. If you look at um the energy
1:01:18demand from data centers this uh fifth
1:01:21bar from the top and one in orange
1:01:22you'll see that there is a demand by
1:01:24about 500 terowatt hours over the next
1:01:28few years and compared to rest of the
1:01:30sectors you can see heavy industry all
1:01:31the way at the top 1500 so about a third
1:01:33of the total demand um of heavy industry
1:01:36is going to be from data centers and
1:01:38this collectively if you look at all the
1:01:40different rows uh the bars that I have
1:01:42that's about 10% of the total demand
1:01:44that we expect globally that's you
1:01:46expect that to be a very very large
1:01:48portion of what is expected to grow uh
1:01:50in terms of demand over the next few
1:01:52years. By few years, this is from 2020
1:01:54for 2030. It's a six-year projection um
1:01:57that came out recently. Um if you look
1:01:59at the data energy growth, um both the
1:02:01US and China really dominate. They are
1:02:04predicted to account for nearly 80% of
1:02:05the global growth in electricity
1:02:06consumption by data centers in the next
1:02:08few years. Okay, you can see the very
1:02:10large demand um in US at the bottom,
1:02:12then China and the rest of um Europe,
1:02:14Asia, etc. uh rest of Asia excluding
1:02:16China you can see where they stand but
1:02:18clearly US and China dominate this by
1:02:21about 80% or so with all of that being
1:02:24said so where is really the energy
1:02:26footprint if you look at AI uh some of
1:02:28us may be using it some of us may stand
1:02:30u a little bit far away from use of AI
1:02:32like myself um but the point is um if
1:02:35you look at different aspects of what
1:02:37most of us may do uh depending on what
1:02:39exactly you're doing you may have a
1:02:41different use of how much energy is
1:02:43being consumed by the particular
1:02:45activity. If you look at this, you have
1:02:47at the bottom a text classification
1:02:48where you're doing something on a
1:02:49textbased search. Um, so if different AI
1:02:52tools have different consumption models
1:02:54based upon the specifics of what is
1:02:56being used and so you see a range of the
1:02:58lowest on text classification, you see
1:03:00somewhere between about 0.5 to a little
1:03:02over one or so. That's the demand in
1:03:05terms of energy consumed to perform a
1:03:07text search about thousand times. So
1:03:08that gives you a range. As you keep
1:03:10going up this particular chart to
1:03:12answering a question or automatic speech
1:03:13recognition or image captioning or image
1:03:15generation which is the worst of all if
1:03:17you use AI to generate an image that's
1:03:19the worst of all you can see how the
1:03:21energy demand associated with that can
1:03:22be several hundreds of um what hours
1:03:26okay so that gives you a sense of what
1:03:28exactly we are doing when you do a
1:03:29search whether it's a textbased search
1:03:31or asking a question or having a
1:03:32conversation with an AI tool so these um
1:03:35numbers give you a spread of these
1:03:37numbers in terms of what the energy
1:03:38demand is M with that um couple of years
1:03:41ago there was a proposed national
1:03:43legislation I think this was under the
1:03:44previous administration um called the AI
1:03:47environmental impacts act of 2024 this
1:03:49was a senate bill introduced by Senator
1:03:51Marky of Massachusetts where he had
1:03:53three primary objectives part of this
1:03:55bill u first it directs the EPA to carry
1:03:58out a study on AI's environmental
1:03:59impacts number one second directs the
1:04:01national institute of standards and
1:04:02technology or NIST to develop standards
1:04:04to measure and report the full range of
1:04:06AI's environmental impacts and the Third
1:04:09is to create a voluntary framework for
1:04:10air developers to report on
1:04:13environmental impacts. Okay, this was a
1:04:15proposed legislation. Of course, it's
1:04:16yet to be passed as you may imagine as
1:04:18of now.
1:04:20So what are the numbers? So now I'll
1:04:22talk um in terms of what the numbers are
1:04:24in terms of what different sources
1:04:25there. There is no central repository of
1:04:27this. The different groups have put
1:04:28together different set of numbers. This
1:04:30is one take on where the numbers are,
1:04:32but I think these are pretty solid in
1:04:34terms of uh where these stand on a
1:04:36relative basis. So you have the first
1:04:38table, the first half of the screen
1:04:40showing the total numbers for the US.
1:04:42Yeah, there about 3,44 data centers,
1:04:45about 1,300 are operating as we speak
1:04:47and about 2,000 being planned. Then I
1:04:49picked up numbers for two different
1:04:51states. One the state of North Carolina
1:04:53where leave where we live in. So that's
1:04:54of interest to us. But also looking at
1:04:56our neighbor to the north, Virginia
1:04:58given that we hear a lot about Virginia
1:04:59and what is going on there. Just kind of
1:05:01give you a perspective and a sense of
1:05:02comparison between North Carolina and
1:05:04Virginia. So you see where North
1:05:06Carolina stands about 65 data centers in
1:05:08the state 13 are operating and about 52
1:05:10being planned. So you do see that quite
1:05:12a lot are being planned in our own
1:05:14state. How does it compare to Virginia?
1:05:16The next row you see very very large
1:05:18numbers state of Virginia right 371
1:05:20versus 458 being planned and um to some
1:05:23degree I've seen numbers where they say
1:05:25the energy demand for the state of
1:05:27Virginia's data centers are larger than
1:05:29many other countries of the world. Okay.
1:05:31Then the second half of the table or the
1:05:33second table looks at the uh number of
1:05:35unique developers in terms of um number
1:05:37of um businesses as well as the
1:05:40operating as well as plan capacity and
1:05:42that gives you a sense of you know the
1:05:43projected growth for the US 61,000 um
1:05:46operating versus 380,000 plants about
1:05:48you know little over um five times
1:05:50growth there in the state of um our own
1:05:53state we go from about 500 to about
1:05:554,000 okay that's another eight times
1:05:57projected growth in terms of what is
1:05:59being planned and then Virginia from
1:06:0117,000 to 37,000 just over 2x in
1:06:04Virginia and I have some examples of um
1:06:07uh the largest that is operating both in
1:06:09the US or and our own states of North
1:06:12Carolina then Virginia up north as well
1:06:14as the largest being planned within the
1:06:15US NC just to give you a sense of how
1:06:18large some of these are in terms of
1:06:20current operating as well as what is
1:06:22being planned down the road
1:06:25okay with that so with that broad
1:06:26landscape now we'll look at what does
1:06:28this mean in terms of data centers and
1:06:30then their impacts on the environment
1:06:31and health. Um I'll go through a um
1:06:35couple of slides with a lot of different
1:06:36bullets. Um given the time that we have,
1:06:38I could be giving an entire hours worth
1:06:40of talk on each bullet on the screen.
1:06:42But what I chose to do today was to give
1:06:45you a broad picture of the various
1:06:46impacts, but then I'll touch up on a
1:06:48couple of those a little bit in detail
1:06:49given the time that we have otherwise
1:06:51you're going to be here for a very very
1:06:52very long day and week or more. Okay. Um
1:06:55the first one of course is the um
1:06:57increased energy demand and the strain
1:06:59on the grid. Um we've talked about a
1:07:01little bit uh with Noah's um excellent
1:07:03briefing before me and you saw some of
1:07:05that earlier. Then um we did talk about
1:07:08um uh noise but again data centers just
1:07:10for the sake of the number of generators
1:07:12the cooling that are running they cause
1:07:14a lot of um noise pollution. Um there's
1:07:17been a lot of articles if you Google
1:07:19data noise pollution you'll see bunch of
1:07:21live videos and audio clips from people
1:07:23who live next to data centers. Um lot of
1:07:25these do exceed the standard 85 decibel
1:07:28threshold which are considered harmful.
1:07:30And if you think about airports and
1:07:32airplane operation around airports, you
1:07:34know um FAA has these um noise visible
1:07:37maps which shows what are the footprint
1:07:39of aircraft around airports when the
1:07:41planes take off and land. What the
1:07:42footprint is in terms of noise pollution
1:07:44of aircraft and then they have used
1:07:46those map to see what are the
1:07:47residential area areas which are right
1:07:49under the planes taking off and landing
1:07:51and what levels of decibb they are
1:07:53experiencing and then there are some
1:07:55mitigation option that FA has to support
1:07:58these communities who live next ports.
1:07:59The point here is data centers cause
1:08:01harmful noise pollution and often these
1:08:03exceed these threshold which are
1:08:05considered harmful for human health. The
1:08:07other aspect of is just given the heat
1:08:09that these generate they enhance thermal
1:08:11pollution and then they cause what are
1:08:13called as heat islands which are
1:08:14basically you know enclose small areas
1:08:17of pocket depending on the size of the
1:08:19um uh energy that is being generated and
1:08:21they have a much larger capacity to
1:08:24store heat which means gets very hot
1:08:26right there. So you have these um data
1:08:28centers when these are very large and
1:08:30have a lot of generators they cause
1:08:31talent. There are a couple of studies
1:08:32that came out recently which documented
1:08:34these and the impacts of this. The next
1:08:36one is a biggie um every one of them
1:08:38biggie but the next one is particularly
1:08:39important for us to think about um
1:08:41impact u data centers impact water
1:08:43availability as well as water quality.
1:08:45Okay, availability. A typical hypers
1:08:47scale data center can use a couple of
1:08:49millions. Sometimes I've seen numbers as
1:08:51high as 5 million gallons of water to be
1:08:53used per day for cooling these towers
1:08:55and and of course it depends on the size
1:08:57of the data center and how much
1:08:58generators they have and so on and so
1:08:59forth. But hypers scale data centers can
1:09:01consume a lot lot lot of water. Okay.
1:09:04Then in terms of quality they also
1:09:06affect water quality. Uh one of the
1:09:07specific pollutants we talked about is
1:09:09depending on what is being used in the
1:09:10data center and the amount of effluence
1:09:12they have. You can have PAS. That's a
1:09:14very very um uh important chemical to
1:09:16think about. Uh these are also called as
1:09:18forever chemicals. These are called
1:09:20forever only because they stay in the
1:09:23atmosphere in the water forever. They
1:09:25don't deteriorate. They don't
1:09:26disintegrate and they cause all kinds of
1:09:28health issues. Tons of studies. Um in
1:09:30our own state in Wilmington, there was a
1:09:32chem plant that had quite a bit of
1:09:34issues. You may have seen um in news out
1:09:36there. So we have those. So based upon
1:09:38the usage of chemicals and materials in
1:09:40a data center facility, you will have
1:09:42airfluent chili pas and that will affect
1:09:44the water quality of downstream. So if
1:09:46you are in apex for example the rivers
1:09:48that go from here, they go to fateville
1:09:50if I remember right. So fate will be
1:09:51talking about hey what's going on with
1:09:53water coming from this part of the
1:09:54state. Okay, there a lot of other toxins
1:09:56uh nutrient loads depending on the air
1:09:58pollution that gets deposited on the
1:10:00water based upon the water cooling you
1:10:02may have acid deposition in the water
1:10:03bodies which leads to other um
1:10:05detrimental impacts. Data centers also
1:10:08cause light pollution uh depending on
1:10:09the height of the building and where
1:10:11they're located. They have these uh
1:10:13buildings which have lights and of
1:10:14course they'll cause light pollution
1:10:15there. Fire risk. This is an important
1:10:17one. We need to think about what are the
1:10:19potential risks due to fire. So when
1:10:21these large data centers with very large
1:10:23generators um catch fire due to an
1:10:25accident or other then you have a
1:10:27serious fire risk which um small towns
1:10:29like Apex I I like to call it small town
1:10:32right I don't think we are large yet um
1:10:34um they have a pretty serious um issue
1:10:36in terms of what needs to be done and
1:10:38the capacity needs to be um managed up
1:10:40front to see how to manage this
1:10:42particular fire should that ever happen.
1:10:44Then um as part of data centers you also
1:10:47have this electricity um transmission
1:10:49high voltage transmission lines which
1:10:50increase the electromagnetic force
1:10:52exposure right so your EMF exposure from
1:10:54high voltage transmission lines. So
1:10:56depending on where these data centers
1:10:57are you may have this HV transmission
1:11:00lines which increase the EMF force um
1:11:02and hence the corresponding exposure to
1:11:04people who live next to that. Continuing
1:11:07on the same list just more of these
1:11:09think about e-waste. There's a lot of uh
1:11:11potential electronic waste comes out of
1:11:12these. we need to think about u proper
1:11:15um uh disposal of these and what may
1:11:17happen in the near- term as well as long
1:11:20term to take care of this e-waste. The
1:11:22next aspect is depending on the various
1:11:24um aspects of what goes into building
1:11:26these uh center generators you may have
1:11:29a lot of um minerals that are being
1:11:31used. So one has to one has to have lot
1:11:33of uh minerals that are exploited um
1:11:36explode and so on. So this will enhance
1:11:38critical mineral exploitation from the
1:11:40earth's resources. The next one is land
1:11:43use degradation conversion. So depending
1:11:45on the kind of land use it may have, we
1:11:47talk about zoning. The town uh looks at
1:11:49zoning issues a lot. So you convert a
1:11:51specific parcel of land from one to the
1:11:53other. And when you do that, you have um
1:11:55various aspects of what happens to the
1:11:56land itself from perhaps an agricultural
1:11:59piece of land um pastures and so on to
1:12:02having more concrete. Now when you have
1:12:03more concrete, you create imperous land
1:12:05which means there are issues with water
1:12:06flow and so on. Okay? So then you have
1:12:08flood risk should there ever be a flood
1:12:10in that part of the state. Then of
1:12:11course when you have land use conversion
1:12:13you displace communities and then you
1:12:14also displace wildlife and natural
1:12:16habitats around the specific location or
1:12:18the parcel of land you're looking at.
1:12:20And the last one is public health
1:12:21impacts. I talked about a lot of
1:12:23environmental issues before this but
1:12:24then you also have significant public
1:12:25health impacts specifically from the
1:12:27emissions that come out of the data
1:12:28centers in terms of what is being
1:12:30combusted if they're combusting anything
1:12:32and the associated with air pollution
1:12:33exposure and then you also have um
1:12:35endocrine disruption based upon the
1:12:37specific chemicals that are being used
1:12:38there. Okay. So this is a broad spectrum
1:12:41of um uh the environmental concerns and
1:12:43one needs to look at um all of them in a
1:12:44very uh detailed manner. Now in terms of
1:12:48air pollution or even thinking about
1:12:49different aspects of the environmental
1:12:50concerns I talked in the last two slides
1:12:53um when you have a generator or a bunch
1:12:55of generators at a specific data center
1:12:58there are multiple variables one need to
1:12:59think about in terms of what really
1:13:00happens at the data center and I listed
1:13:02a few here. The first one is fuel type.
1:13:04Okay we we I think this is a very
1:13:05obvious one. Most of us know this and
1:13:07Noah touched upon this um this a little
1:13:09bit earlier in his talk. So the type of
1:13:11fuel that is being used by data center
1:13:13is something to think about. So diesel
1:13:14is the one that's most commonly used. Um
1:13:17then comes natural gas which get a
1:13:18little bit cleaner but still it is
1:13:20fossil fuel at the end of the day. Uh
1:13:21then fuel cell which um bring out
1:13:23hydrogen. Then um terms of renewables
1:13:26there is something called as
1:13:27hydrogenated vegetable oil. Okay some um
1:13:29places use them. Uh then there could be
1:13:31a whole lot of other renewables. So one
1:13:33need to think about what is the specific
1:13:35type of fuel that is being used for data
1:13:37center and hence what are the associated
1:13:39environmental health impacts. Then the
1:13:41next variable to think about is what is
1:13:42the capacity right both in terms of the
1:13:44total capacity for example the proposed
1:13:47new data center which was withdrawn the
1:13:49capacity was 300 megawatt and then it is
1:13:52not a single unit of 300 megawatt they
1:13:54talked about how there could be multiple
1:13:56smaller generators in this example I
1:13:58think they proposed 100 or so of three
1:14:00megawatt capacity so you have multiple
1:14:02generators each of some capacity 1 2 3
1:14:04megawatt and so on then you have a whole
1:14:06bunch of those 100 200 300 depending on
1:14:08what is the size the third one is how
1:14:10you configure the specific generator on
1:14:13site. Right? So in this example, there
1:14:15was discussion of having four buildings
1:14:16if I remember right and four buildings
1:14:18will have somehow 100 generators
1:14:19distributed across the four buildings.
1:14:21And then when you have four buildings,
1:14:22100 generators, you have to think about
1:14:24what is the specific configuration each
1:14:26stack because that leads to different
1:14:27dispersion parameters. So what is the
1:14:29stack height? What is the stack
1:14:30diameter? What is the exit gas velocity?
1:14:32What is the exit temperature and so on.
1:14:34So those determine the dispersion and
1:14:35hence the associated air pollution that
1:14:37come from the stack. So again think
1:14:40about what is the specific configuration
1:14:41for each of these um generators. The
1:14:44next one is duration of the run. Okay
1:14:46depending on the configuration and the
1:14:48need and how they integrate with the
1:14:49grid or not you have to think about how
1:14:52long these generators run and the
1:14:55associated air pollution exposure is a
1:14:56function of whether these are continuous
1:14:58or they do start stop and so on and they
1:15:00all have different impacts. Then
1:15:02depending on any or all of the uh four
1:15:06bullets above the last one is what are
1:15:08the pollutants emitted based upon the
1:15:09fuel type. Um you have no knock socks
1:15:12PM2.5. I'll talk about PM2.5 in a minute
1:15:14a little bit more. That's fine
1:15:15particulate matter of size 2 and a half
1:15:17microns which includes multiple
1:15:19pollutants and the most important one is
1:15:20black carbon or soot then CO CO2 and so
1:15:23on. So when you talk about air quality
1:15:26impacts um I touched upon briefly in the
1:15:28last slide. Um there are multiple
1:15:29pollutants that affect human health. Um
1:15:32NOx, SO2, CO, PM2.2 and so on. There is
1:15:35also CO2 uh carbon dioxide. It's a
1:15:37climate pollutant or greenhouse gas
1:15:38pollutant. And I I won't discuss um
1:15:41greenhouse gas impacts a whole lot in
1:15:43this discussion only because I want to
1:15:44focus on one aspect a lot more which is
1:15:46air pollutant that affect human health.
1:15:48But CO2 is a climate pollutant. It has
1:15:49long-term impacts and that's not
1:15:51something to be discarded easily. Okay.
1:15:54Then the duration of genital runs and
1:15:55hence exposure have different impacts.
1:15:57You have both short-term which is acute
1:15:59impact based upon exposure to something
1:16:01really bad over one or two hours or
1:16:03long-term chronic impacts where you
1:16:05expose something over days or a year
1:16:07depending on the specific pollutant. The
1:16:09US EPA regulates six different air
1:16:12pollutants through what are called as
1:16:13national ambient air quality standards
1:16:15where they have very rigorous science
1:16:17which supports how human health is
1:16:18affected based upon exposure to air
1:16:20pollutant and based upon multiple
1:16:22epidemiological studies, risk assessment
1:16:24studies and so on. They have come up
1:16:25with uh what are called as knacks or
1:16:27standards that protect human health. Six
1:16:30are regulated by the EPA and the states
1:16:31in turn have to um uh come up with plans
1:16:34to make sure they meet these air
1:16:36pollutant standards for different
1:16:37pollutants. For example, NO2 one gas
1:16:40pollutant has both a short form or an
1:16:42acute 1 hour standard as well as a
1:16:45chronic or an annual national ambient
1:16:47air quality standard. Similarly, PM2.5
1:16:49has both a daily standard, which is what
1:16:51you're exposed over a period of a day,
1:16:5324 hours, as well as over an annual or
1:16:55long-term period um annual next.
1:16:59So, what is PM2.5? You heard about this
1:17:01quite a bit um both earlier by Noah and
1:17:03myself and maybe in previous town
1:17:04council meetings. So, PM2.5 is one of
1:17:07the most complex air pollutant you can
1:17:09think of. Okay. In terms of ename health
1:17:11risk, this is the number one killer of
1:17:13people in the world with about 8 million
1:17:16people dying prematurely every year
1:17:18because of exposure to PM2.5. That's a
1:17:20number just broadly speaking um uh
1:17:22globally within the US we lose about
1:17:25100,000 people every year approximately
1:17:27every year due to exposure to this
1:17:29particular political PM2.5. Okay. Now
1:17:31what is PM2.5? Look at the picture on
1:17:33the right. If you look at this brownish,
1:17:35you know, irregular shape polygon, that
1:17:37is a picture of a beach sand. Typical
1:17:39size of beach sand, which is about 80
1:17:41microns or um in size. Then the one next
1:17:44to it is a typical human hair strand, a
1:17:48single strand of human hair. That's
1:17:49about 50 to 70 microns. That's a
1:17:51thickness of a single human hair. And
1:17:53then within a single human hair strand,
1:17:54you can think of putting six different
1:17:56balls. Those are blue color balls on the
1:17:59extreme right there. And those are
1:18:01particles called as PM10 or fine
1:18:03particulate matter of size 10 microns.
1:18:06So these were the ones that people are
1:18:07thinking about 20 25 years ago as big
1:18:10particles that affect air pollution. But
1:18:11right now that is not much of an issue
1:18:13right now. But if you take one PM10 ball
1:18:15the blue ball within one PM10 you can
1:18:18fit four small red balls. That's your
1:18:21PM2.5. So that's the smallest part you
1:18:23can think of in terms of this particular
1:18:25airplane impact. So each orange or red
1:18:29ball that you see is your PM2.5. That's
1:18:31the size that you can think of. Um this
1:18:34is a well-known adverse air pollutant
1:18:36for human health and it's being
1:18:38regulated both in the US and by World
1:18:40Health Organization. The next level of
1:18:42um PM 2.5 or PM is what is called ultra
1:18:46fine particles. These are particles even
1:18:48smaller less than 100 microns. Right? Um
1:18:51so we won't talk about them for now. So
1:18:52we'll just focus on PM 2.5. But I will
1:18:55say there's emerging evidence where
1:18:56ultrafine particles also cause adverse
1:18:58human health. Okay, for sake of this
1:19:00discussion, PM2.5 is both a solid as
1:19:04well as a liquid particle in the air.
1:19:05They measure about 2 and a half
1:19:06micrometers or microns uh in diameter.
1:19:09These includes particles both that are
1:19:11directly emitted from any combustion,
1:19:12right? You have a combustion process,
1:19:13these are directly emitted as well as
1:19:15they get resuspended from the road dust.
1:19:17Right? When you have a car go by, you
1:19:19have dust there and then you have the
1:19:20resuspension goes on. that's also um uh
1:19:22directly um emitted. Then you also have
1:19:25PM that is formed from conversion of
1:19:27gases such as sulfur dioxide, nitrogen
1:19:30dioxide, ammonia, vol organic component
1:19:31so on. These go through atmospheric
1:19:33process physical as well as chemical
1:19:35conversion and they form another
1:19:37component of PM2.5 and we put all these
1:19:40together and that's your total PM which
1:19:42is both directly emitted particle as
1:19:44well as something that gets converted
1:19:45from gases through atmospheric process
1:19:47and they come in many sizes and shapes
1:19:49and composed of hundreds of chemicals
1:19:51because just lot of different particles
1:19:52right but given the small size the
1:19:55important part here is they can
1:19:56penetrate deep into the body mostly
1:19:58through inhalation right um and then
1:20:00based upon the size they go into the
1:20:02lungs and then as they get smaller they
1:20:05can easily break what is called the
1:20:06bloodb brain barrier. Once they go to
1:20:08the brain you have all kinds of effects
1:20:10on the human body. Okay, that's your
1:20:11PM2.5 sort of um primer. So what are the
1:20:15impacts of PM2.5? They have both acute
1:20:17as well as chronic exposure effects.
1:20:20Acute you have respiratory irritation,
1:20:21asthma and COPD um uh flare-ups,
1:20:24cardiovascular stress and so on. So
1:20:26basically they increase the risk of
1:20:27non-fatal heart attacks and irregular
1:20:28heartbeats. Um from chronic or long-term
1:20:31exposure which is over a year you get
1:20:33both heart and brain damage lung
1:20:34conditions gets um worse cancer risk and
1:20:37then systemic illness such as diabetes
1:20:40adverse birth outcomes and so on. So
1:20:41basically the emerging literature says
1:20:43there are more and more adverse health
1:20:45impacts that people are facing based
1:20:47upon exposure to PM 2.5 um including um
1:20:51the brain related issues such as
1:20:53dementia and sometimes decreased
1:20:55capacity to learn in children who live
1:20:57next to schools okay when you have high
1:20:59traffic um uh um emissions associated
1:21:01with the schools and then you have
1:21:03children their capacity to learn goes
1:21:05down and the documented studies that
1:21:07look into that so who is at risk to PM2
1:21:09exposure you have children and the
1:21:10elderly people with pre-existing health
1:21:12conditions like asthma or heart disease.
1:21:14Healthy individuals are also at risk
1:21:16especially with long-term exposure.
1:21:18Okay, so that's the population you want
1:21:19to think about. Then a little bit on NO2
1:21:22another gas pollution I want to think
1:21:23about only because this is also
1:21:24important from a diesel combustion point
1:21:26of view from a data center as well as
1:21:28from natural gas. Short-term effects um
1:21:30airway irritation, asthma flare up, lung
1:21:32function drops when you get more
1:21:33exposure to um you know to a short time.
1:21:36Uh long-term effects, you have new
1:21:38incense of asthma. healthy individuals
1:21:40start to get asthma, lung damage,
1:21:42chronic disease, um ongoing exposure to
1:21:44chronic lung disease, heart problem and
1:21:45so on. The single most important effect
1:21:48of NO2 is asthma. Okay, both in children
1:21:50and adults. Uh people who don't have
1:21:52asthma get asthma um incidences. People
1:21:55who do asthma have asthma exacerbation
1:21:57based upon exposure to NO2. Okay. So,
1:21:59children and older adults are most
1:22:00suscept susceptible to these uh
1:22:02pollutants and people with asthma like I
1:22:04said they face severe reactions even at
1:22:06low pollutant levels.
1:22:08So one study which is being
1:22:10peer-reviewed um I like to always focus
1:22:12on peer-reviewed studies but there's a
1:22:14study that's being peer-reviewed right
1:22:15now which said that based upon growth of
1:22:17data centers in the US they will cause
1:22:20about 600 asthma symptom cases new
1:22:22incident of asthma as well as about 1300
1:22:25premature deaths in 2028 and the total
1:22:27public health costs can exceed $20
1:22:29billion um based upon um uh value they
1:22:33put to human life as well as the medical
1:22:34costs associated with adverse health
1:22:36impacts. Um this particular impact this
1:22:39particular number seems to be an
1:22:40increase over 200% from 2023 when they
1:22:42last did this when the stationary while
1:22:45the stationary fuel combustion related
1:22:46health cost will increase only 17%.
1:22:48Think about that. So stationary fuel
1:22:51source combustion that's like the power
1:22:52plants and other industrial sources they
1:22:54increase health risk only by 17%. But
1:22:57the growth in data centers would be
1:22:58200%. It's about you know 12 times
1:23:00higher number than the 17% from um
1:23:03stationary source fuel combustion. Okay
1:23:05this is not uniform. I have a map coming
1:23:07up on the next slide which basically
1:23:08says well that's a broad big picture
1:23:09number across the country. The highest
1:23:11county level cost is seven times the
1:23:13national average means the effects are
1:23:16not uniform across the country. There
1:23:18are some counties some people are more
1:23:20vulnerable to this than others based
1:23:21upon either their health conditions or
1:23:23where they live based upon other social
1:23:24demographic and so on. And this highest
1:23:26county level cost is 200 times the
1:23:29lowest country call. So it's not uniform
1:23:31and the point I want to make is these
1:23:32are broad national numbers but there's
1:23:34quite a bit of spread that one needs to
1:23:36think about in this set of numbers. So
1:23:38this is the breakdown of that. So 23 on
1:23:40the left in the in the bar charts and
1:23:42then the uh green and orangish color
1:23:44show how the low and high range can grow
1:23:47based upon this projected increase in
1:23:49emissions from data centers. The middle
1:23:51um map of the US shows the per household
1:23:54health cost. You can see the
1:23:55northeastern US roughly the uh what is
1:23:57called the Ohio River Valley. We have
1:23:59bunch of power plants there. But also
1:24:00based upon this particular study, they
1:24:02showed the per household health cost can
1:24:04be pretty high in that part of the
1:24:05country. And the top 10 counties are on
1:24:07listed on the right there in terms of
1:24:09where you'll have the most impacts. And
1:24:11look at the um 10 counties there. Seven
1:24:15or eight or those are in West Virginia.
1:24:17Okay. Why West Virginia? Anybody wants
1:24:20to guess?
1:24:21>> Cold.
1:24:22>> Coal. But also the demographics of
1:24:25people there in general you have a lot
1:24:26poorer people who have more you know
1:24:29baseline health insurance not being good
1:24:30when they're exposed to more air
1:24:32pollution you have more health insurance
1:24:33there right so that's that's why popping
1:24:35up like that so so the per household
1:24:37health cost basically the point is to
1:24:39show that vulnerable populations may
1:24:41have more exposures and hence more
1:24:42health risk right and that this this
1:24:44analysis clearly shows that so the per
1:24:46household cost varies from about 300 um
1:24:49uh from 245 to 332 for the top 10
1:24:51counties but that's the spread that you
1:24:53But this could be about 200 times worse
1:24:55than the lowest county.
1:24:59Okay. Now, let's switch to Apex. Okay.
1:25:01And for this, um, I'll start with a map
1:25:04that shows the Southern Environment Law
1:25:05Center to see what they saw as the
1:25:08existing proposed data centers for the
1:25:10southeastern US, basically the region
1:25:11that they focus on. That's the map on
1:25:13the left. On the right is a little bit
1:25:14zoom into our own part of the state. Um
1:25:16you see the new hill digital campus was
1:25:19proposed and then withdrawn in the lower
1:25:21left corner of the right hand map. You
1:25:23see the other data centers in the rest
1:25:24of this um region.
1:25:27So what I did um in the last couple of
1:25:30weeks was to do some additional
1:25:32modeling. Uh I'll show some results. Um
1:25:34I have a bunch of charts coming up next.
1:25:36But what I did was to think about how
1:25:38the data center may operate. Um you
1:25:40heard quite a bit from Noah earlier talk
1:25:42about base load and backup Z and so on.
1:25:44So basically um my version of this is to
1:25:46talk about base load option one where
1:25:48the data centers draw the power from the
1:25:50grid and in this case Duke energy if if
1:25:52that's a facility because that's what we
1:25:54heard that the developer had an
1:25:56agreement with Duke at some point to
1:25:58have additional generation to meet the
1:26:00demand and with this base option one u
1:26:03power being drawn from the grid you
1:26:04address both routine as well as a peak
1:26:06demand during extreme weather. Some of
1:26:09us may recall the early part of this
1:26:11year when there was a cold snap and
1:26:13anyone recalls a message on your TV
1:26:16phones and so on about conserve energy
1:26:18conserve energy right that was a cold
1:26:20snap we had that came from u the
1:26:22utilities right and the state so when
1:26:25you have uh a data center like this
1:26:26running with the base um load being
1:26:28drawn from the grid you may have
1:26:29additional demand going on okay peak
1:26:32demand in both extreme weather hot and
1:26:33cold u base load option two is where we
1:26:36have the so-called behind the meter We
1:26:38talked a little bit earlier with Noah.
1:26:40So where the proposed data center
1:26:42generates the power onsite behind the
1:26:44meter but in that case they have to
1:26:46develop new infrastructure on site.
1:26:48Okay, which doesn't exist as of now. And
1:26:50the third one is where we have the
1:26:51backup generation onsite which is really
1:26:54backup the base floor coming either from
1:26:55options one or two. The backup is what I
1:26:58think is of concern to a lot of people.
1:26:59Not to mention that the first two
1:27:01options are not of concern.
1:27:03Base floor option one. Okay. This will
1:27:05lead to excess emissions and potential
1:27:07violation of the national ambient air
1:27:09quality standards in the region. Okay.
1:27:11So basically when you have uh Duke
1:27:13committing to take on more um generation
1:27:15of power it has to come at some cost
1:27:17right what are they burning so they have
1:27:19to do something to bring on uh more
1:27:21consumption um and then that comes at
1:27:23some cost because right now no Duke
1:27:26facility other than shareh nuclear and I
1:27:28don't think nuclear is renewable either
1:27:30right so the point is um this will lead
1:27:32to excess emissions and potential
1:27:33violation of the standards and I want to
1:27:35talk a little bit about what this means
1:27:37for violation of air quality standards
1:27:39when a region is designated to be in
1:27:40violation of the national ambient air
1:27:42quality standards of pollutant. Okay. So
1:27:43you have a region like let's say the
1:27:45Raleigh Durham metro area if this is in
1:27:47violation of the standards for air
1:27:48pollution for a given pollutant this
1:27:50region will go through substantial
1:27:52adverse impacts from both an economic
1:27:54and public health point of view. Okay.
1:27:56Until measures are in place to reduce
1:27:58emissions from cultable sources where
1:28:00the state works in partnership with the
1:28:02facilities and the industries um and
1:28:03other sources in the region to see what
1:28:06needs to happen to bring the area into
1:28:08attainment of the standard. So that's
1:28:10when the state works with the local
1:28:11agencies to come up with what is called
1:28:12as a state implementation plan. So when
1:28:14you have excess emissions in the region
1:28:16based upon what Duke or another facility
1:28:18may be doing, you have excess emissions
1:28:19which may lead to violation of the
1:28:21standard based upon what they are doing.
1:28:23So many years ago um ozone was a key
1:28:25pollution of concern for North
1:28:26Carolina's urban areas including the
1:28:28triangle, the tri and the Charlotte.
1:28:29These three areas had significant ozone
1:28:31problems some time back. And then in the
1:28:34year 2002 a historic legislation was
1:28:36passed what is called as the clean smoke
1:28:38stacks act that was under partnership
1:28:40from the state utility commission uh and
1:28:42EMC environmental management commission
1:28:45I think uh they work with the uh
1:28:47facility at that time Duke energy and
1:28:49Carolina power at that time to pass a
1:28:51historic legislation where they had a
1:28:53mandate um to reduce NOx emissions
1:28:56significantly from the 14 coal burning
1:28:58power plant in the state uh both Knox
1:29:00and socks were reduced uh this was in
1:29:022002 too. And then based upon those
1:29:05projected emissions reductions, you
1:29:07know, we did a bunch of analysis and
1:29:08modeling. Um I was um um part of the
1:29:11analysis way back then and at that time
1:29:14we projected that the state will um
1:29:16attain the air quality standards for
1:29:17ozone in the year 2012. And guess what?
1:29:20In the year 2012, by Duke Energy
1:29:24reducing its power plants and putting a
1:29:25lot of controls on them over time for
1:29:27reduced oxen socks, the state's air did
1:29:29become clean by the year 2012. There's
1:29:32another study which also looked at the
1:29:33impacts of PM2.5 sulfate reductions and
1:29:36they also quantified that there were
1:29:38substantial health benefits in the
1:29:39state's residents due to reduction of um
1:29:42uh knocks and socks from these power
1:29:44plants and at that time they um
1:29:46estimated that about 1,700 premature
1:29:48debts are being awarded annually due to
1:29:50clean air in the state. Okay. So as a
1:29:52function of all of that um I'm happy to
1:29:54tell that the state today is an
1:29:55attainment of all national I mean air
1:29:57quality standard. This is from the
1:29:58NCDAQ. Um we are having clean air
1:30:01everywhere for all criteria pollutants.
1:30:03But again this is based upon a standard
1:30:05there's an emerging evidence that you
1:30:07know no nonzero value is good for us.
1:30:11Okay no non-zero value is good for us.
1:30:14So even though it's a standard which
1:30:15says you have adverse health impacts
1:30:17above a threshold even lower levels of
1:30:19concentration of pollutant you do have
1:30:20adverse health impacts.
1:30:23>> Now base floor option two. So this is
1:30:25where uh we have on-site generation
1:30:27using fossil fuels such as natural gas
1:30:28or other. But then when you have that
1:30:30you also have to think about what are
1:30:32the local environmental concerns as a
1:30:34function of on-site generation. Okay. Um
1:30:36there was a proposed um natural gas
1:30:39power plant just over 3,000 megawatt
1:30:42natural gas power plant uh in um one of
1:30:45the counties in Virginia just across the
1:30:46border from this um from North Carolina
1:30:49in the north. And this is Pennsylvania
1:30:51County. And based upon this proposal,
1:30:53they were going to generate um uh power
1:30:55by burning natural gas for this
1:30:57capacity. And they estimated about 326
1:30:59tons of excess PM emissions. And then
1:31:01based upon a study that was commissioned
1:31:03by the Southern Environment Law Center,
1:31:04they basically found that if you look at
1:31:06the map on the right, there'll be about
1:31:081.28 million people downwind of this
1:31:11facility who will have additional
1:31:12exposures. um about half of those
1:31:14impacts were in the state of Virginia
1:31:16and the rest of them find their way
1:31:18across the border into North Carolina
1:31:20and a very small percentage of South
1:31:21Carolina as well. And then they
1:31:22estimated that the total health impacts
1:31:24of this is about $31 million over one
1:31:26year or 625 million by the year 2040.
1:31:30Okay, that's what they estimated. The
1:31:31point of this is to show that even when
1:31:33you have on-site generation and when you
1:31:34use fossil fuel, you will have health
1:31:36impacts both in the near field and far
1:31:38field depending on the strength of the
1:31:40facility as well as how far the winds
1:31:41go. Okay.
1:31:43And just in terms of what these numbers
1:31:45mean, 326 tons um and $31 million. Think
1:31:48of every ton of PM emissions having
1:31:51about $100,000 in health costs. Just
1:31:54ballpark, right? One ton of PM emissions
1:31:57has about $100,000 in health costs. And
1:31:58you can do the scaling depending on how
1:32:00you want to look at the numbers.
1:32:03All right. New case studies. This is
1:32:04where uh uh I I looked at this
1:32:06particular um proposed facility and now
1:32:08withdrawn and then did a bunch of
1:32:10modeling to give um a sense of what
1:32:13these impacts may be for um the town and
1:32:16neighbors um here. So this withdrawn
1:32:19project um probably everybody in this
1:32:20room knows what this facility was all
1:32:22about. Uh located on 190 acres which is
1:32:24zone for industrial employment um
1:32:26located between US1 and old US1 just
1:32:28west of Sharon Harris. um they proposed
1:32:30uh to construct four 200,000 square foot
1:32:33buildings and it'll have diesel backup
1:32:34generator. That's what they proposed
1:32:36equipped with multiple emissions
1:32:37controls to meet this EPA tier 4
1:32:39standards. Okay. And these controls were
1:32:41supposed to um reduce emitted
1:32:43pollutants. That's what they proposed.
1:32:46So what I did was use an EPA dispersion
1:32:48model. This is called air mod. It's a
1:32:50regulatory model that EPA has. This what
1:32:52is used for local scale dispersion. Um
1:32:54it's a standard uh model that EPA has
1:32:56developed over the years. I've been
1:32:58involved with some of the development
1:32:59and application with EPA. Uh but
1:33:01basically what we did was to um estimate
1:33:03the emission dispersion from backup
1:33:04generation using air mod which calculate
1:33:06the dispersion of pollutants for
1:33:08research and regulatory purposes and the
1:33:10outputs are vared based upon the knack
1:33:12uh the national ambient air quality
1:33:13standard which is based upon the best
1:33:16scientific understanding of the adverse
1:33:17impacts of air pollution and determines
1:33:19whether an area is within attainment.
1:33:20Okay. So to do the modeling uh compile
1:33:24information based upon existing case
1:33:25studies at other data centers to see
1:33:27what are the type of interest they use
1:33:29what are the configuration they use and
1:33:30then um use a few different
1:33:32configurations um and then scale these
1:33:34emissions based upon the proposed um
1:33:36capacity here to align with the
1:33:38previously proposed new digital campus.
1:33:41So um I I ran three different um
1:33:43simulations here um two using diesel and
1:33:46the third using natural gas. I just call
1:33:48them as configurations one, two and
1:33:49three. Basically um each of the three
1:33:52configurations have very different stack
1:33:53configurations, different um number of u
1:33:56facilities, different number of
1:33:57generators, different uh stack diameter,
1:33:59stack height and so on. basically uh um
1:34:01picked another published study which is
1:34:03used for permitting elsewhere and use it
1:34:05to see what will happen if they use the
1:34:06exact one here because I don't think the
1:34:09developer who applied to the town of
1:34:11Epics gave a lot of these details right
1:34:12so we had to go find something else from
1:34:14outside because they didn't go to the
1:34:15permitting phase of this particular um
1:34:17issue um in each case the capacity of
1:34:19each was 3.1 megawatt then this is
1:34:22something I came across and I'm open for
1:34:23discussion here when a data center
1:34:25proposes um capacity of 300 megawatt um
1:34:28I've seen some evidence to show that
1:34:30they actually need to plan for
1:34:31redundancy of 600 megawatt. Okay. So to
1:34:35account for the potential redundancy um
1:34:37did the modeling two different ways. N
1:34:39is where I stick to 300. So you have 97
1:34:41generators each of 3.1. The 2N is
1:34:44basically where you're doubling the
1:34:45capacity and I have 184 generators each
1:34:48um generally 3.0 megawatt. Then um
1:34:51diesel 2 is a second configuration. Then
1:34:53natural gas 3 is a different
1:34:54configuration but using natural gas for
1:34:56um combustion.
1:34:58Um before we go into the specifics of
1:35:00this particular modeling for this
1:35:01facility I want to talk about how
1:35:03dispersion works. This is a notional
1:35:05plot um which shows how dispersion
1:35:07works. Top left shows two different
1:35:10locations of um power plants or points.
1:35:12I call them as points because you have a
1:35:14specific location a specific stack and
1:35:16then it has some stack parameters. It's
1:35:18burning something and then depending on
1:35:20how the winds blow, how the atmosphere
1:35:22works, how the dispersion works. Um you
1:35:25look at then the top left panel how the
1:35:27dispersion goes on a single hourly time
1:35:29scale based on how the mutology or the
1:35:31winds are blowing you see these two
1:35:33plumes like shooting out of those two
1:35:35particular points that's how point
1:35:36source dispersion works right and then
1:35:38on the right instead of two points if
1:35:40you have a low-level area source which
1:35:43is basically sort of a something spread
1:35:44over a um larger area lot of small
1:35:46sources instead of modeling each source
1:35:48separately just put a large area source
1:35:50over some area and then based upon the
1:35:52height it's usually a lower level source
1:35:54opposed a point source which is elevated
1:35:56right so um with a very similar strength
1:35:58on the right you have a hourly
1:36:00dispersion from a low level source on
1:36:01the right if you look closely you'll see
1:36:03this greenish polygon in the middle of
1:36:05this figure if I can sort that's that's
1:36:07the source definition and from there you
1:36:09have early dispersion then the same two
1:36:12source types point on the left and area
1:36:14on the right are shown as um annual
1:36:17dispersion in the bottom right you see
1:36:19what happens over a period of one year
1:36:20and how the dispersion works after you
1:36:22do the dispersion based on ambient
1:36:24methology and the source is continuously
1:36:26emitting some pollutant right and and
1:36:28see how it works over a period of one
1:36:29year and you see how the plume patterns
1:36:31change over what happens over one year
1:36:33versus 1 hour I want to show this to
1:36:35make a point that depending on remember
1:36:37I earlier talked about how long the
1:36:39facility is running the running
1:36:41continuous start stop 1 hour 2 hour 4
1:36:44hours later and so on so I want to think
1:36:45about how the dispersion works at
1:36:47different time scales and where the
1:36:49plumes may go so on the left if you look
1:36:51at the plume center line the Nox it can
1:36:53be about 1 ppb at the plume center line
1:36:55whereas on an annual time scale is
1:36:57only.1 ppbpb. So you see how the numbers
1:37:00go down depending on what is the
1:37:02temporal metric you look at. On the
1:37:04right you have the same numbers for the
1:37:06area source which is a low-level source
1:37:07which is a irregular shaped green color
1:37:09polygon I showed. So the point again is
1:37:11show that you know dispersion works
1:37:12differently for different source type
1:37:14and it's very important to know how a
1:37:16proposed data center configures their
1:37:17sources.
1:37:19Okay. All right. So here's my study
1:37:22domain. Um uh it's basically the center
1:37:24of this concentric circles is where the
1:37:27proposed new campus was. And if you look
1:37:30closer um um you'll see those four
1:37:32different dots that represent the four
1:37:33buildings. And what I did here was to
1:37:35show concentric circles of 1 kilometer
1:37:37apart starting from the proposed
1:37:39facility and then um so on the left
1:37:41figure is a 10 km radius going out from
1:37:43the proposed facility in New Hill. on
1:37:45the right is a 5 km. Same thing but just
1:37:47five kilometers. And what we did was in
1:37:49this modeling to put receptors in every
1:37:51one of those circles at different
1:37:52distances um from the center and then
1:37:55see how dispersion works from the
1:37:56facility and see where the impacts may
1:37:58be. Now where we are right now if you
1:38:00look at this so on the left panel this
1:38:02is uh that's the proposed facility new
1:38:04hill um which was proposed and withdrawn
1:38:06and we are roughly this building is
1:38:09about here where the exis just about 12
1:38:12km or so from where the facility was.
1:38:14Okay, that's our current location right
1:38:16now where X of the word apex is. Okay,
1:38:19so just to give you the coordinates. So
1:38:20what I'll do next is show a series of
1:38:22colorful maps which show how the
1:38:24pollution works from the proposed
1:38:26facility on the left at 10 km at those
1:38:29concentric 1 km incremental circles.
1:38:33Okay. So now we'll look at NOX
1:38:35dispersion. So I'll focus on two
1:38:36different NOX and PM2.5. And then NOX
1:38:39goes on to form NO2 for which we have
1:38:41the standard nitrogen dioxide. So um
1:38:44these three different figures show how
1:38:46the dispersion worked for the three
1:38:48configurations I talked about. DC1, DC2,
1:38:51DC3. Uh DC 1 and two burn diesel, the
1:38:54NC3 burns natural gas and looking at a
1:38:57um plume based upon running the
1:39:00dispersion for one full year, but then
1:39:02pick out for over a period of one year
1:39:05what is a single worst case hour. Okay,
1:39:09looking at the most extreme case you may
1:39:10have and what is the single most extreme
1:39:12hour to see what may happen based upon
1:39:14the exposure to based upon this
1:39:16particular um dispersion coming from the
1:39:18source. So if you look at DC1 and DC2 um
1:39:20where I'm drawing these red holes you
1:39:22see the max goes from about 196 um uh on
1:39:26the left to about 179 in the middle
1:39:28that's in parts per billion and the
1:39:30standard is 100 parts per billion. So
1:39:32you see all nonzero values which are
1:39:35shown are values above 100. Right? If
1:39:37you look at the legend box in the
1:39:38extreme right, the blue is starts
1:39:40starting at 100 and we go up to about
1:39:41little over 180 uh in red. So you see
1:39:44values which are you know roughly in the
1:39:46southern quadrant of where the source
1:39:47was and these values are at 196 at a
1:39:50maximum or 179 and the national ambient
1:39:53air quality standard for you know KNOX
1:39:55is 100 right so I'm showing always above
1:39:57100 then now if you look at uh what will
1:40:00happen if you double the capacity
1:40:02remember I talked about the redundancy
1:40:03that um some facilities talk about so if
1:40:06you want to have 300 megawatt you
1:40:07actually want to have capacity for 600
1:40:09megawatt so now you have 184 um number
1:40:12of generators each at 3.1. Now the
1:40:14entire 10 km radius you see is now
1:40:16colored um in a nonzero value and
1:40:19they're all over 100. I can see where
1:40:21the um concentrations are. Look at the
1:40:23maxima um 389 on the left and then um
1:40:26359 on the right. So configuration two
1:40:29drops the maxima a little bit but not a
1:40:31whole lot. But in natural gas on the
1:40:33right you don't see a whole lot of
1:40:34action happening based upon this
1:40:36configuration.
1:40:37PM 2.5 that's the pollut we talked about
1:40:39quite a bit or fine particulate matter.
1:40:42um single hourly maxima. Um we have 15
1:40:45on the left with configuration one and
1:40:47then 13 in configuration two. And again
1:40:49you see that while the hot spots you
1:40:52know the reddish orange are in the um
1:40:54southern uh half of the um circle you do
1:40:57see this yellowish green coming u away
1:40:59from the facility towards east and
1:41:01north.
1:41:04Um this is comparing um uh 2x. Now last
1:41:07one was single x or 300 megawatt. was
1:41:09600 megawatt and now the um maxima have
1:41:12gone up even higher than what you saw
1:41:13last time to 29.99 in DC1 and 27.64 in
1:41:18DC2.
1:41:19Now what I did was um since facilities
1:41:23don't run for a full year, they run for
1:41:24a few hours, right? Based upon the
1:41:26backup generation model. So what I did
1:41:28was configure the model to say I'll run
1:41:31for four hours at a stretch, right? and
1:41:33then run for multiple four hours over
1:41:35the entire year and find the maximum of
1:41:37those multiple four hours. So
1:41:39potentially what you're looking at is if
1:41:41the facility would run only for four
1:41:42hours during the year, what is the worst
1:41:44case based upon dispersion conditions,
1:41:46right? So there are limits that
1:41:48different um um towns, counties have in
1:41:51terms of how long these generas can run.
1:41:52Um for example, south coast, one of the
1:41:54basins there in California have a limit
1:41:56of 200 hours as a maximum they can run
1:41:59for a year. Um I don't remember if the
1:42:01town of Apex has one, right? But the
1:42:03state I believe has 50 um hours they can
1:42:05run a backup generator. So we need to
1:42:07see what are the appropriate um numbers
1:42:09we want to use for backup generation.
1:42:11How long they can run. In this case I'm
1:42:13running for 4 hours and see what is the
1:42:14worst four 4hour case. And now the
1:42:16maxima go from uh 119 on the left to
1:42:19109. So still you get values that are
1:42:21exceeding this threshold of 100. Okay.
1:42:25Now PM 2.5 again the same for our uh
1:42:28discussion. Um 9 on the left and then
1:42:308.43 43 um in the middle.
1:42:33Now what I did was okay you have all
1:42:35these uh spatial plots look at different
1:42:36numbers. Now I say okay let me just put
1:42:38them all together and see okay across
1:42:40all the receptors that I modeled okay
1:42:42how does it compare based upon
1:42:43threshold. So this is just if you look
1:42:45at the first one these are called as box
1:42:47and whisker plots. You just look at the
1:42:48distribution of the entire data. The
1:42:50first one DC1 you do see the maxima you
1:42:53know exceeding the red line. Red line is
1:42:54a threshold of 100 um uh in that case uh
1:42:57where they exceed this uh a little bit
1:42:58over. Then the middle one is a
1:43:00configuration two which is dropping the
1:43:02overall distribution slightly smaller.
1:43:03So you get a sense of what is the
1:43:05general range of numbers that each of
1:43:06the configuration do uh to the NO2
1:43:09maximum.
1:43:10Now on the right is where you go with
1:43:12the redundant capacity where you're
1:43:14doubling the capacity from 300 megawatt
1:43:16to 600 megawatt and again you have
1:43:18significant number of locations which
1:43:19are exceeding the threshold. You see the
1:43:21whole number of dots here um going up to
1:43:24194 and then up to 179 in the middle.
1:43:28Now this is a comparison of 1 hour
1:43:30versus the 4 hour um average maxima and
1:43:32again in this case you see 1 hour on the
1:43:34left 98 and 89 the right 71 and 77
1:43:40and then this is the last one for PM 2.5
1:43:42to see how the PM varies. So basically
1:43:43what I did was the point of these
1:43:45analysis to show that depending on the
1:43:48source configuration depending on the
1:43:50time metric you're looking at 1 hour 4
1:43:52hour annual you do get different impacts
1:43:54okay and from health point of view you
1:43:55have to think about what is it really
1:43:56important for what you're looking at and
1:43:58see how this may affect human output
1:44:02so moving on um I want to alert um the
1:44:05board um to um two different activities
1:44:08happening at the state level one is the
1:44:10North Carolina's um artificial
1:44:12intelligence leadership council. This is
1:44:14convened by um um our governor and under
1:44:17the DIT. uh they have a they put out a
1:44:20strategic road map recently and they
1:44:22focus on three different broad
1:44:24objectives to protect uh which focus on
1:44:27safeguarding North Carolina residents
1:44:28responsible AI use in strong risk
1:44:30mitigation practices and then to prepare
1:44:32uh where you strengthen the AI literacy
1:44:34and readiness of students workers and
1:44:35communities and then transform the
1:44:36outlines of how the state can modernize
1:44:39leverage AI but under protect the first
1:44:41goal they have multiple goals in each of
1:44:43these objectives the first goal is to
1:44:45protect residents from AI harms so it is
1:44:47called out in the strategic roadmap map
1:44:49um but we need to think about how we go
1:44:50about the protection part of what this
1:44:52um road map lays out. The second
1:44:54activity at the state level is this
1:44:56energy policy task force um they put an
1:44:57interim report um earlier this year.
1:44:59Some of you may have seen this.
1:45:01Basically what they said is significant
1:45:03load growth is coming to North Carolina
1:45:05associated with opportunity and risks.
1:45:07The figure on the shows um shows the an
1:45:09the figure on the right shows the annual
1:45:11CO2 emissions from electricity
1:45:13generation North Carolina. we see this
1:45:14very nice drop off starting from 2005
1:45:172023 or so but then they say after 23 uh
1:45:21for the next few years you'll have a
1:45:22leveling off of the CO2 emission because
1:45:24that's what the projections for the
1:45:26growth is and then after that it'll
1:45:28start to drop after 2030 or so. So while
1:45:30the statewide increase is um was only 7%
1:45:33earlier now we expect a growth of 16 to
1:45:3660% over the next two decades. Okay,
1:45:37that's what is being um looked at by the
1:45:40task force and the large fraction of
1:45:42this particular load growth is due to
1:45:43data centers and other large loads.
1:45:46Okay, so to wrap up um environmental
1:45:49public health impacts of data centers is
1:45:50substantial. Okay, I think I I've shown
1:45:52quite a bit of evidence for that. Um
1:45:54AI's power demand is new territory for
1:45:56the town, for the state and for the
1:45:58nation. Okay, permitting decisions for
1:46:00DCs need to account for both the
1:46:01environmental and public health costs
1:46:03and these are real costs of society.
1:46:04These are not fictional statistics
1:46:06numbers. These are real costs. People
1:46:08have adverse costs based upon these
1:46:09exposures. And the configuration of data
1:46:11centers can vary widely. I demonstrated
1:46:14that with my tests and moving power
1:46:16generation to meet excess demand from
1:46:17grid to local on-site may have its own
1:46:19un intended adverse impacts. And both
1:46:22the state and the town such as Apex, we
1:46:24need to review the permit application
1:46:26carefully to assess impacts and minimize
1:46:27public health impacts to protect
1:46:29vulnerable population. Okay. One needs
1:46:31to quantify all known adverse effects
1:46:34and have appropriate plans for
1:46:35mitigation.
1:46:37And how do we promote sustainable growth
1:46:39of AI industry while meeting energy
1:46:41demand? Um review the progress being
1:46:42made at the state level. Uh the two um
1:46:45resources I touched upon the energy
1:46:46policy task force and the AI leadership
1:46:48council for their recommendations and
1:46:50other legislative updates. But at the
1:46:52end I think we want to explore how to
1:46:54promote this industry for its alleged
1:46:56benefits to society such as jobs, taxes,
1:46:58etc. without compromising both the
1:47:00environment and the public health of its
1:47:02citizens. With that, here is my take on
1:47:06a data center.
1:47:09>> Okay. Thank you.
1:47:11Happy to answer questions.
1:47:15>> I want to first thank both our speakers.
1:47:17You know, a lot of town councils don't
1:47:19have an environmental advisory board. So
1:47:23um you know while many are in
1:47:25moratoriums right now, they they might
1:47:28want to consider you know
1:47:31having environmental advisory boards and
1:47:33having speakers like you and Noah here
1:47:36um to speak. you know, you and I
1:47:38actually spoke a little bit last year
1:47:40when this one was proposed
1:47:43and, you know, concerns of things from
1:47:47taking environmental studies uh in
1:47:49college, thinking of um Love Canal and
1:47:52and what that does to an area. I mean,
1:47:54and that's very different than obviously
1:47:56a data center, but it does um cause a
1:47:59lot of the same health issues. Um, I was
1:48:02in Marvel, North Carolina this past
1:48:04weekend and that is actually where one
1:48:06of the largest in North Carolina is. Um,
1:48:11I got to drive up to it and hear the
1:48:13noise that it actually produced and
1:48:15actually have a connection to somebody
1:48:17there that's dealing with both cancer
1:48:19and asthma. Um, is it from the data
1:48:24center or is it just uh issues that were
1:48:27already there with this person? that I
1:48:29don't know but you did um raise a
1:48:33question that I have for you. Um is
1:48:36there any scenario under which a hypers
1:48:38scale data center will not have any
1:48:40adverse health effects uh to residents
1:48:43in the town of Apex?
1:48:50>> Not with the current technologies being
1:48:51proposed and used.
1:48:54>> Okay. Uh clearly not. um you you saw
1:48:57that based upon configurations the most
1:49:00popular fuel types are diesel, natural
1:49:02gas that's what there is some evidence
1:49:04of using fuel cell but again I don't
1:49:07think it's um scalable we need to see um
1:49:10what will come out of this um and then
1:49:12depending on um the specific size I
1:49:15don't see it happening right now but I
1:49:18think I'm always counting on human
1:49:20ingenuity
1:49:22which means sometime soon some smart
1:49:25mind somewhere will figure out what is
1:49:27the best way to do this and do exactly
1:49:29what you just asked.
1:49:30>> Okay. But doesn't exist right now.
1:49:34>> Thank you.
1:49:34>> You talked about EPA
1:49:37air quality standards and stuff. Um,
1:49:41>> do you know of any communities who
1:49:44impose stricter standards than what the
1:49:47EPA has or are they limited by what the
1:49:50EPA requires?
1:49:51>> The state of California. Okay.
1:49:54>> They are ahead.
1:49:55VP,
1:49:56>> right? Uh and some towns locally have
1:49:59their own they call them air basins or
1:50:01air districts and they have much
1:50:03stricter um they call state standards or
1:50:06air basin standards which are usually
1:50:07more stringent than EPA and they have
1:50:09been the leader for a large degree the
1:50:11past several decades California right
1:50:14but California is California and EPA is
1:50:16EPA right I
1:50:17>> I was I was thinking more lo local
1:50:19communities like Apex or
1:50:22>> I'm not aware of a local
1:50:25community like Apex having something
1:50:26most important.
1:50:29>> Well, I mean air quality, I mean
1:50:33it's hard to build a wall around the
1:50:35town and keep the air quality,
1:50:38>> right? But but there have been there
1:50:39have been instances where a specific
1:50:42town has come up with stringent
1:50:44standards for some sector of the fossil
1:50:48fuel. For example, building emissions,
1:50:49right? Uh we use heating and cooling for
1:50:51buildings, right? So some cities, towns
1:50:54of the country have come up with
1:50:56standards which are you know have for
1:50:57permitting a building to have some
1:51:00heating cooling. They come with more
1:51:02progressive standards to see how the
1:51:04town can build before you give a permit
1:51:05to a developer to have something.
1:51:07>> These are standards you have to follow
1:51:08and some there are examples I don't have
1:51:10it handy right now. I'm happy to share
1:51:12those examples of how a local town a
1:51:14local municipality becomes something
1:51:16more stringent for developing building
1:51:17standards.
1:51:20>> That that would be helpful.
1:51:24So looking at your maps, it kind of
1:51:26looked like the most effective
1:51:28protection that an individual could do
1:51:32for themselves is just to be as far away
1:51:34as possible from one a facility that
1:51:37emits um as you modeled.
1:51:40>> Yeah.
1:51:42>> Um
1:51:43are there any other industries that are
1:51:46comparable that you sort of see the same
1:51:48pattern in emissions? Because this is
1:51:51sort of like a new thing. Is there
1:51:52anything else that you could say? Well,
1:51:55this is sort of an apple to an apple.
1:51:58Would it be like a coal fired power
1:52:00plant or are you talking like
1:52:02>> Yeah. Yeah. Yeah. Coal fire power
1:52:04plants. They they are um slightly
1:52:06different beast in the sense that these
1:52:07are usually tall one or two stacks,
1:52:10right? I talked about the clean smoke
1:52:12stacks act of 2002 when we had 14 coal
1:52:15burning power plants. But a power plant
1:52:17is a facility which are multiple stacks
1:52:19but not 100 to 300. They have two,
1:52:21three, four, five stacks at the most in
1:52:23the facility. These are really tall,
1:52:25right? Um 100 ft or more and they put
1:52:28out emissions at at that stack based
1:52:30upon what they're combusting and then
1:52:32based upon the height. The reason they
1:52:33are tall is so that they push the
1:52:36pollution up there and then they get
1:52:37dispersed further down. You saw my maps,
1:52:39right? So that's how they get dispersed,
1:52:40right? But at a low level, this is a
1:52:43unique situation with these data
1:52:45centers, right? Because you have
1:52:46multiple small genators all in a very
1:52:49small space,
1:52:52right? Multiple. Think of a 300 megawatt
1:52:55going to have 100 different genative
1:52:56each generating 3 megawatt, right? So
1:52:59this is unique.
1:53:09>> Thank you so much. Thank you. Appreciate
1:53:10it.
1:53:10>> Very informative.
1:53:11>> Very help.
1:53:18>> So,
1:53:20anything else?
1:53:22>> No, just you know, the state of North
1:53:24Carolina, the way our laws and what
1:53:26we're allowed to regulate is passed
1:53:27down, has to be conferred or allowed by
1:53:29the state itself. And so, some examples
1:53:31might be really good to look at to see
1:53:32what other cities around the country are
1:53:34doing, but we not may not be applicable
1:53:36to North Carolina as well.
1:53:38>> It would have to be applicable to us for
1:53:40sure
1:53:41>> if we can do anything.
1:53:45>> So it's sort of becoming clear that uh
1:53:49this sort of whole on-site generation
1:53:52like this is coming up later. This is
1:53:54not a discussion we were having when the
1:53:57new health thing um was proposed.
1:54:01>> It was simply backup or emergency
1:54:03generation
1:54:04they were proposing at the time. So
1:54:07early on you sort of talked about
1:54:10different flavors of data centers and
1:54:13frontiers, but I'm wondering does a
1:54:15component have of that have to be are
1:54:18you do you plan on on-site generation
1:54:21and what does that look like? What what
1:54:23fuels are you talking about here? Right.
1:54:26Um versus just strictly emergency aside
1:54:30from defining what exactly is an
1:54:32emergency.
1:54:33>> Wow. Yeah.
1:54:37I think it's it's it's going to be
1:54:39difficult
1:54:43to try to insist on on
1:54:48more of a renewable
1:54:50uh generation system unless you're
1:54:53talking pure batteries.
1:54:55uh simply because of of
1:54:59the density of of of the apex area, I
1:55:02don't think you're going to be able to
1:55:03find enough
1:55:07land mass uh to come up with something
1:55:10uh
1:55:12to avoid either diesel or or some sort
1:55:15of natural gas, propane, LG
1:55:19types of uh power.
1:55:24But then does it become is it an
1:55:27appropriate thing given the development
1:55:30pattern to even say yeah sure you can
1:55:34have on-site generation or should that
1:55:36be like a just a non-starter
1:55:40>> that may be something you're not able to
1:55:42regulate the state who writes the
1:55:44permits for those things would regulate
1:55:46it. So I think um all this good
1:55:48information, something we could consider
1:55:50and think about maybe more at a town
1:55:51level would be um the quality of
1:55:54standards for the generators themselves,
1:55:56the type of fuel that potentially could
1:55:58be used, the distribution of data
1:56:01centers, whether one or multiple, where
1:56:03they're located, um how they set up
1:56:05their sites, which we've kind of talked
1:56:06about as land use goes, where they're
1:56:08located. Um, and I mean that proposed
1:56:11data center, we're going to keep the
1:56:13generators within the confines of the
1:56:15building. I mean, the buildings were
1:56:17going to be outside of where the
1:56:18generators were located.
1:56:21And that's one thing I did like about
1:56:23that proposal
1:56:26that would that would help with so like
1:56:28they built them internal to the the
1:56:30primary structures that helped with the
1:56:32noise aspect of it.
1:56:33Now, I don't know if you're also
1:56:35creating a more concentration of the
1:56:37fumes going up and that
1:56:39>> probably would. Yeah. I mean, you're
1:56:42creating a a tunnel going up.
1:56:47>> That makes it really important to have a
1:56:50distance threshold from sensitive,
1:56:53>> right,
1:56:53>> places like outdoor recreation, schools,
1:56:56I would imagine, the hospital, um,
1:56:59places like that.
1:57:11I mean, one thing that I've been a
1:57:13little worried about on on these rules,
1:57:16the envir environmental issues and and
1:57:19the air quality and and water quality
1:57:21are are
1:57:24paramount, I think, but I think the town
1:57:27itself has a lot of constraints on what
1:57:30it can and cannot
1:57:32I think I think that's why it's
1:57:33important that we we've been talking
1:57:35about this for so long. We'll continue
1:57:36to talk about this and we've had experts
1:57:37show up to talk about this is because
1:57:39there are a lot of things that we're not
1:57:41going to be able to do from a regulatory
1:57:42standpoint, but we can have the
1:57:44conversation. We can make our elected
1:57:46officials aware of it. We can let our
1:57:48residents know be aware of it. And then
1:57:49there are some of these things that we
1:57:50could still try and be see if we could
1:57:52work into as zoning conditions given
1:57:54that potentially if if council decides
1:57:56to move forward data in whatever form,
1:57:58it'll probably be regulated to a heavy
1:58:00industrial area which does not exist on
1:58:02the on the map right now.
1:58:03>> And so that would be a new resoning. And
1:58:05so we would have we could come up with a
1:58:08list of proposed suggested zoning
1:58:10conditions for data center specifically
1:58:13to help address some of these things
1:58:15where we couldn't maybe regulate that
1:58:16directly through the UDO amendments
1:58:18themselves.
1:58:20But that again, we'll have to we'll have
1:58:21to come up with those ideas.
1:58:23>> Whole new set.
1:58:24>> Yeah.
1:58:26>> I'm not going to be on that task force.
1:58:30>> Well, we as part of this process, we'll
1:58:32draft the UDO amendment and we'll draft
1:58:34suggested zoning conditions. Yeah.
1:58:36>> And that'll go to planning board and
1:58:37council to discuss further
1:58:40>> be subject to public hearings where
1:58:41people can come and speak of whether
1:58:42it's a whether what's been proposed is a
1:58:44good idea or whether it doesn't do
1:58:45enough.
1:58:53Um,
1:58:54>> is there anything from from these two
1:58:56presentations
1:58:57other than I know there's like a kind of
1:58:59a wait now just hearing like any type of
1:59:02any type of new element being introduced
1:59:04causes issues and health issues. Like is
1:59:06there anything specifically that you
1:59:08heard from either of our two speakers
1:59:09that you would like followup information
1:59:11or anything on?
1:59:18I mean maybe as more information
1:59:23comes about since this is such a new
1:59:25subject for everyone that anything they
1:59:28come across they would share with us
1:59:31you know I think that would be helpful
1:59:33>> um he uh Dr. Rob he had mentioned an
1:59:38inreview report uh paper right now. I
1:59:40can share that with you. I found another
1:59:41paper from Harvard. I'll share that with
1:59:43you guys as well and I'll put that on
1:59:44the website that's speaking directly to
1:59:46the impact data centers on public health
1:59:48and things like that. And we'll probably
1:59:49see more of this because it becomes
1:59:51community part of the local national
1:59:53conversation.
1:59:59I I just all of this is very fascinating
2:00:02this evening, but before I came here
2:00:04tonight, I had the television on in the
2:00:06background and and there was a
2:00:07commercial for I don't know, ChatGT or
2:00:09something like that. And you know,
2:00:11they're they're they're talking about,
2:00:12oh, you know, go on it and and talk
2:00:14about what your dog's Halloween
2:00:16costume's going to be and and just, you
2:00:18know, after seeing that and sitting
2:00:20there thinking, why? [laughter]
2:00:29When is our next meeting?
2:00:30>> Yeah, I can pull it up on the screen for
2:00:32everyone who's here.
2:00:43So, um, tomorrow,
2:00:46September 9th, we'll be doing a 12:00
2:00:48EAB resident call on Teams. Um, so
2:00:50that's been the invite has been sent
2:00:52out. If anyone has not gotten that
2:00:53inveter, would like to be included and
2:00:54they have not signed up, they can email
2:00:56me directly. My email is all over the AB
2:00:59data center web page and I'll send make
2:01:01sure that they get an invite for that.
2:01:02We'll be talking about um topics that
2:01:05were brought up the last two meetings,
2:01:06the one we had in the second and today.
2:01:07They'll be able to provide some input
2:01:09and feedback and then our next actual
2:01:11meeting like this one here will be on
2:01:13October 7th in this room and we'll be
2:01:15talking about noise.